| 2015-01-16 09:48:46 | RESIDENTIAL (R2) AWNING BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- ENGINEER TO PROVIDE ORIGINAL SEAL AND SIGNATURE ON |
| | PLANS AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE. |
| | |
| | 2- ENGINEER TO SPECIFY ALL DESIGN CRITERIA INCLUDING |
| | AWNING LOCATION ON THE BUILDING (HEIGHT) AND THE |
| | EXPOSURE CATEGORY AS REQUIRED BY SEC. 3105.4 OF 2010 |
| | FBC-BUILDING. |
| | |
| | 3- AWNINGS TO BE APPROVED BY THE DESIGNER OF RECORD. |
| | SEC. 107.3.4.2 OF CITY AMENDMENTS TO FBC. |
| | |
| | 4- ARCHITECTURAL DRAWINGS SUBMITTED NEED TO BE SIGNED |
| | AND SEALED AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE. |
| | (NOTE: DRAWING MAY NOT BE SIGNED AND SEALED IF THE |
| | ARCHITECT STAMPS THE DRAWING WITH THE REVIEW STAMP |
| | REQUIRED ON ITEM #3 ABOVE). |
| | |
| | 5- A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS |
| | SHOWING HOW THE FABRIC COVERED STRUCTURE IS DESIGNED |
| | FOR A QUICK REMOVAL OR BREAKAWAY ( A SERIES OF CLEAR |
| | PHOTOGRAPHS SHOWING THE DESIGN AND THE REMOVAL PROCESS |
| | IS ACCEPTABLE ALSO). SEC. 3105.4.2.1 OF 2010 FBC. |
| | |
| | B) PROVIDE LETTER SIGNED BY THE BUILDING OWNER STATING |
| | THAT THE FABRIC WILL BE REMOVED IN THE EVENT OF 75 MPH |
| | WINDS. SEC. 3105.4.2.1 FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |