Plan Review Notes
Plan Review Notes For Permit 15010184
Permit Number 15010184
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-17 12:01:581) A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1 OF
 THE 2010 FL. PLUMBING CODE.
 2) A MINIMUM OF TWO DRINKING FOUNTAINS SHALL BE
 PROVIDED PER THE 2010 FL. ACCESSIBILITY CODE SEC.
 211.2.
 3) A BACKFLOW PREVENTION DEVICE SHALL BE INSTALLED ON
 THE WATER SERVICE TO THE UNIT. A MINIMUM OF A DOUBLE
 CHECK VALVE ASSEMBLY SHALL BE REQUIRED PER THE CITY OF
 WPB CROSS CONNECTION MANUAL.
 4) INDICATE ON THE PLANS IF THE UNIT IS GOING TO HAVE A
 SANITARY SEWER CONNECTION OR CONNECTED TO A HOLDING
 TANK. IF CONNECTED TO A HOLDING TANK INDICATE THE SIZE
 OF THE TANK ON THE PLANS. A PERMIT FROM THE PALM BEACH
 COUNTY HEALTH DEPARTMENT MAY BE REQUIRED.
  
 PLUMBING PLAN REVIEW