2015-01-26 07:13:54BUILDING PLAN REVIEW
 PERMIT: 15010184
 ADD: 3775 N. MILITARY TRL
 CONT: KENNEDY HOMES, LLC
 TEL: ( 561)613-6917
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 26/ 2015
 ACTION: DENIED
  
 1) THE LENGHT OF TIME THIS MANUFACTURED BUILDING IS TO
 BE ON SITE HAS NOT BEEN PROVIDED, IF TEMPORARY OR NOT.
 THE DEFINITION OF TEMPORARY:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 108.1
 GENERAL. THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A
 PERMIT FOR TEMPORARY STRUCTURES AND TEMPORARY USES.
 SUCH PERMITS SHALL BE LIMITED AS TO TIME OF SERVICE,
 BUT SHALL NOT BE PERMITTED FOR MORE THAN 6MONTHS.
  
 FOR THE PURPOSE OF THIS REVIEW, THE LENGHT OF TIME WILL
 NOT BE TEMPORARY OR THE MANUFACTURED BUILDING WILL BE
 ON SITE OVER 6 MONTHS OF USAGE.
  
 THE S1 SHEET SHOWS A FOUNDATION SYSTEM THAT WILL BE
 USED FOR TEMPARAY FOUNDATIONS, THIS SYSTEM DOES NOT
 COMPLY WITH SECTION 2010 FBC-B
 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM).
  
 2) THE MANUFACTURED BUILDING PLAN IS A STATE APPROVED
 PLAN. SHEET 1 OF 4 INDICATES SITE INSTALLED ITEMS THAT
 ARE NOT PART OF THE STATE APPROVAL:
  
 2A) COMPLETE FOUNDATIONSUPPORT AND TIE -DOWN
 2B) RAMPS. STAIRS HANDRAILS & GUARDRAILS
 2C) STORM SHUTTERS & GUTTERS
 2D) STORM SHUTTERS
  
 3) THE MANUFACTURED BUILDING SHOWS (2) EXITS, NOTE ON
 THE PLANS INDICATES METAL STAIRS TO CONSTRUCTION OFFICE
 BY OTHERS, PLEASE PROVIDE COMPLIANCE WITH, 2010 FBC-B:
 1009.4 STAIR TREADS AND RISERS. STAIR TREADS AND RISERS
 SHALL COMPLY WITH SECTIONS 1009.4.1 THROUGH 1009.4.5.
  
 1012.1 WHERE REQUIRED. HANDRAILS FOR STAIRWAYS AND
 RAMPS SHALL BE ADEQUATE IN STRENGTH AND ATTACHMENT IN
 ACCORDANCE WITH SECTION 1607.7. HANDRAILS REQUIRED FOR
 STAIRWAYS BY SECTION 1009.12 SHALL COMPLY WITH SECTIONS
 1012.2 THROUGH 1012.9. HANDRAILS REQUIRED FOR RAMPS BY
 SECTION 1010.8 SHALL COMPLY WITH SECTIONS 1012.2
 THROUGH 1012.8.
  
 1013.1 WHERE REQUIRED. GUARDS SHALL BE LOCATED ALONG
 OPEN-SIDED WALKING SURFACES, INCLUDING MEZZANINES,
 EQUIPMENT PLATFORMS, STAIRS, RAMPS AND LANDINGS THAT
 ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED
 VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT
 WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF
 THE OPEN SIDE. GUARDS SHALL BE ADEQUATE IN STRENGTH AND
 ATTACHMENT IN ACCORDANCE WITH SECTION 1607.7.
  
 4) SHEET S1 ON THE OVERALL STAIR AND RAMP DETAIL:
 4A) PLEASE PROVIDE A BOTTOM LANDING TO THE RAMP IN
 COMPLIANCE WITH2010 FBC-B 1010.6 LANDINGS. RAMPS SHALL
 HAVE LANDINGS AT THE BOTTOM AND TOP OF EACH RAMP,
 POINTS OF TURNING, ENTRANCE, EXITS AND AT DOORS AND IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 ACCESSIBILITY. LANDINGS SHALL COMPLY WITH SECTIONS
 1010.6.1 THROUGH 1010.6.5.
  
 4B) 1010.6.4 CHANGE IN DIRECTION. WHERE CHANGES IN
 DIRECTION OF TRAVEL OCCUR AT LANDINGS PROVIDED BETWEEN
 RAMP RUNS, THE LANDING SHALL BE 60 INCHES BY 60 INCHES
 (1524 MM BY 1524 MM) MINIMUM.
  
 4C) THE ACCESSIBLE DOORWAY NEXT TO THE RAMP IS LOCATED
 18 INCHES FROM THE BEGINNING OF THE RAMP. FBC-B
 1010.6.5 DOORWAYS. WHERE DOORWAYS ARE LOCATED ADJACENT
 TO A RAMP LANDING, MANEUVERING CLEARANCES REQUIRED BY
 ICC A117.1 ARE PERMITTED TO OVERLAP THE REQUIRED
 LANDING AREA. FL. ACCESSIBILITY CODE FIHURE 404.2.4.1
 (H) LATCH APPROACH, PULL SIDE.
  
 4D) THE DETAIL # 1 SHOWS A 2X4 TO BE USED AS A
 HANDRAIL, PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1012.3
 HANDRAIL GRASPABILITY TYPE I OR TYPE II.
  
 4E) SHEET S1 DETAIL # 3 SHOWS STAIRS WITH A HANDRAIL
 THIS IS TO BE AN ACCESSIBLE STAIR IN COMPLIANCE WITH
 2010 FBC- 1012.6 HANDRAIL EXTENSIONS.
 HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING
 SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN
 ADJACENT STAIR FLIGHT OR RAMP RUN. WHERE HANDRAILS ARE
 NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL
 EXTEND HORIZONTALLY AT LEAST 12 INCHES (305 MM) BEYOND
 THE TOP RISER AND CONTINUE TO SLOPE FOR THE DEPTH OF
 ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS WHERE
 HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE
 HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING
 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF
 RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE
 SAME DIRECTION OF THE STAIR FLIGHTS AT STAIRWAYS AND
 THE RAMP RUNS AT RAMPS.
  
 4F) NOTE # 3 INDICATES THE LIVE LOADS AT 60 PSF, PLEASE
 REVIEW THE 2010 FBC-B TABLE 1607.1(35) STAIRS 100 PSF
 STAIRS AND EXITS.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  