| 2015-01-23 14:44:27 | 600 OKEECHOBEE BOULEVARD |
| | PERMIT #15010175 |
| | MASTER #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL: ALL AREAS OPEN TO THE PUBLIC OR OCCUPIED BY |
| | WORKERS WITH HEARING CHALLENGES SHALL PROVIDE FIRE |
| | ALARM VISUAL NOTIFICATION AND IS SUBJECT TO INSPECTOR'S |
| | FIELD VERIFICATION. |
| | |
| | SHEET FA-002: MISSING SYMBOL FOR MANUAL PULL STATION. |
| | |
| | SHEET FA-100: MISSING NOTIFICATION APPLIANCE IN POOL |
| | EQUIPMENT ROOM (NOT SHOWN ON PLAN) AND UNIFORM ISSUE |
| | #B010. |
| | |
| | SHEET FA-100: COULD NOT LOCATE ANY TAMPER SWITCHES IN |
| | THE FIRE PUMP ROOM. |
| | |
| | SHEET FA-101A: INSUFFICIENT NOTIFICATION IN EAST |
| | PORTION OF CONNECTOR #156. |
| | |
| | SHEET FA-101A: EXTERIOR PULL STATION AND NOTIFICATION |
| | NEEDED NEAR POOL EXIT/CONNECTOR #156. |
| | |
| | SHEET FA101B: STROBE DEVICE IN NORTH CORRIDOR IS |
| | LOCATED MORE THAN 15 FEET FROM THE END OF THE CORRIDOR. |
| | |
| | SHEET FA-101B: INSUFFICIENT NOTIFICATION IN BAR TERRACE |
| | #105A. |
| | |
| | SHEET FA-101B: THE FIRST FLOOR HAS A LARGE QUANTITY OF |
| | WINDOWS/NATURAL LIGHTING. RE-EVALUATE THE STROBE |
| | CANDELA ESPECIALLY THE CEILING-MOUNTED DEVICES. |
| | |
| | SHEET FA-101C: SOUTH WALL OF BALLROOM HAS INSUFFICIENT |
| | STROBE COVERAGE. |
| | |
| | SHEET FA-101C: SOUTHWEST AREA OF LOADING #131 HAS |
| | INSUFFICIENT STROBE COVERAGE. |
| | |
| | SHEET FA-101C: NORTH WALL OF SECURITY #133 HAS |
| | INSUFFICIENT STROBE COVERAGE. |
| | |
| | SHEET FA-101D: NO NOTIFICATION APPLIANCE IN LOBBY OF |
| | SERVICE ELEVATOR #111 OR STAIR VESTIBULE #163. |
| | |
| | SHEET FA-101D: INSUFFICIENT STROBE COVERAGE IN ADMIN |
| | OFFICES #112. |
| | |
| | SHEET FA-102A: MISSING NOTIFICATION APPLIANCE WITHIN 15 |
| | FEET OF CORRIDOR DOOR IN PRE-FUNCTION CORRIDOR #221. |
| | |
| | NOTE: 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE |
| | EMERGENCY COMMAND CENTER: |
| | (1) THE FIRE DEPARTMENT COMMUNICATION UNIT |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT, AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE |
| | (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS |
| | FOR THE BUILDING |
| | |
| | NOTE: 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING |
| | DEVICES OR FUNCTIONS SHALL BE PROVIDED WITHIN THE |
| | EMERGENCY COMMAND CENTER: |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT |
| | (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE |
| | ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |