| 2015-05-07 17:32:02 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE |
| | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE |
| | REQUIRED BY CHAPTER 471, FLORIDA STATUTES & 61G15 |
| | FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA |
| | STATUTES & 61G1 FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 2) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 3) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 4) FBC-R314.3.1 WHEN ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | 5) FBC- 107.3.5.3 - ELECTRIC SERVICE RISER WITH WIRE |
| | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE |
| | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. |
| | |
| | 6) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE |
| | ELECTRICAL EQUIPMENT ON THE PLANS. |
| | |
| | 7) SPECIFY THE LOCATIONS OF THE ELECTRIC SERVICE METER |
| | AND PANELS ON THE ELECTRICAL PLANS. FBC 107.2.1 |
| | |
| | 8) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH |
| | CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLETS. |
| | |
| | 9) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 10) NEC 406.8 - OUTDOOR RECEPTACLES ARE REQUIRED TO BE |
| | WEATHER PROOF. |
| | |
| | 11) NEC 440.11 & 440.14 SHOW THE LOCATION OF THE |
| | REQUIRED A/C EQUIPMENT DISCONNECTING MEANS ON THE |
| | PLANS. |
| | |
| | 12) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP |
| | RECEPTACLES SHALL BE SUPPLIED BY NO FEWER THAN TWO |
| | SMALL APPLIANCE BRANCH CIRCUITS. |
| | |
| | 13) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 14) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 15) NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE |
| | AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR |
| | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| | LESS. |
| | |
| | 16) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 17) NEC 210.52 (C) (1) - A RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH COUNTERTOP SPACE 12 INCHES OR WIDER |
| | SO THAT NO POINT ALONG THE WALL LINE IS MORE THAN 2 |
| | FEET MEASURED HORIZONTALLY FROM A RECEPTACLE OUTLET IN |
| | THAT SPACE. |
| | |
| | 18) NEC 210.52(A) - (H) SHOW COMPLIANCE WITH REQUIRED |
| | RECEPTACLE OUTLET SPACING. |
| | |
| | |
| | |
| | |
| | |
| | |