| 2015-05-07 17:07:46 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY MECHANICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING |
| | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS |
| | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. |
| | PROVIDE EQUIPMENT SIZING CALCULATIONS. |
| | |
| | 2) FBC - 107.3.5.3 PROVIDE TWO SETS OF A MECHANICAL |
| | PLAN TO SHOW EQUIPMENT AND LOCATION AND DUCT SYSTEMS |
| | PER FBC-R M16. SHOW CLOTHES DRYER AND BATH EXHAUST PER |
| | FBC-R M15. |
| | |
| | 3) FBC-R - M1305.1.3 APPLIANCES IN ATTICS. |
| | ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN |
| | OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE |
| | ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT |
| | NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES |
| | (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG |
| | MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM |
| | THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE |
| | CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5 |
| | NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE |
| | SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES |
| | (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE |
| | APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS |
| | OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY |
| | 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW |
| | REMOVAL OF THE LARGEST APPLIANCE. |
| | |
| | 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT |
| | BEDROOMS. |
| | |
| | 5) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING |
| | PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, |
| | SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | |
| | 6) FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| | AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| | OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. |
| | |
| | 7) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLANS THAT |
| | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. FBC |
| | 107.2.1 |
| | |
| | 8) PROVIDE AN ANCHORING DETAIL FOR THE MECHANICAL |
| | EQUIPMENT THAT IS LOCATED ON THE EXTERIOR OF THE |
| | BUILDING. FBC-R M1307.2.1 |
| | |
| | |
| | |