| 2015-01-26 16:18:54 | BUILDING PLAN REVIEW |
| | PERMIT: 15010153 |
| | ADD: 610 CLEMATIS ST |
| | CONT: CAN COPE CONSTRUCTION |
| | TEL: (561)201-9319 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | DATE: FRI. FEB. 06/2015 |
| | ACTION: DENIED |
| | |
| | SUBMITTED IS A SPECIFICATION FOR 6MM CORK SOUND TEST |
| | ASTM E 492-09 ACCEPTED |
| | |
| | 1A) COMPLIED. FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) COMPLIED, FBC-B 2010 603.2 EXCEPTION (2) TILE |
| | FLOORING. INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 2) NO TEST SUBMITED!!! FOR FLAME SPREAD. FLAME SPREAD |
| | INDEX. A COMPARATIVE MEASURE, EXPRESSED AS A |
| | DIMENSIONLESS NUMBER, DERIVED FROM VISUAL MEASUREMENTS |
| | OF THE SPREAD OF FLAME VERSUS TIME FOR A MATERIAL |
| | TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | "NONCOMBUSTIBLE" DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS |
| | |
| | FBC-B 2010 |
| | JAMES A. WITMER CBO |