| Date |
Text |
| 2015-01-30 05:34:21 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S |
| | SPECS/INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER |
| | FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.107.2.1.2ND |
| | REQUEST. THERE WERE NO SPEC/MANUAL ATTACHED. |
| | 2) SHOW THE REQUIRED KNEE & TOE CLEARANCE DIMENSIONS |
| | FOR THE LAVATORIES AND THE DRINKING FOUNTAINS ON SHTS. |
| | A-4.1 & A-4.2. COMPLY W/ FL. ACC. CODE SEC. 306. 2ND |
| | REQUEST. |
| | 3) SHT. A-4.1 - ELEVATIONS # 3 & # 4 - TYPO -THERE ARE |
| | IDENTIFICATION ARROWS AND ITEM NAMES ON THE PLANS |
| | POINTING TO NOTHING. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 4) SHT.A-4.2 - RESTROOM #122 IS CALLED OUT AS A UNISEX |
| | RESTROOM. PER SEC.403.5.2 & 403.5.3 OF 2010 FPC, A |
| | UNISEX TOILET ROOM SHALL INCLUDE ONLY ONE WATER CLOSET |
| | AND ONE LAVATORY (AND ONE URINAL PER EXCEPTION). UNISEX |
| | BATHING ROOMS SHALL ALSO INCLUDE ONE WATER CLOSET AND |
| | ONE LAVATORY. THIS RESTROOM DOES NOT MEET THE |
| | DEFINITION OF A UNISEX RESTROOM. COMPLY WITH THE STATED |
| | PUMBING CODE SECTIONS. |
| | 4) SHT. A-4.2 - SHOW THE WIDTH OF THE ACCESSIBLE SHOWER |
| | IN ROOM # 122. MINIMUM WIDTH SHALL BE 30 INCHES. FAC |
| | SEC.608.2.2. 2ND REQUEST. |
| | 5) SHT.A-4.2 - ELEVATION #4 R.R. 122- TYPO - SHOWS BOTH |
| | URINALS AS ADA ACCESSIBLE BUT ONE DOES NOT COMPLY.MAX. |
| | HEIGHT TO THE RIM SHALL BE 17 INCHES. FAC SEC.605.2. |
| | 6) SHT.A-4.2 - THE ACCESSIBLE SHOWER SHALL HAVE A |
| | MINIMUM 60 INCH WIDE ENTRY ON THE FACE OF THE SHOWER |
| | COMPARTMENT PER THE FAC SEC.608.2.2. THE LAVATORY |
| | APPEARS TO ENCROACH IN THIS SPACE. CLARIFY. |
| | 7) SHT.A-4.2 - THE ACCESSIBLE SHOWER SHALL HAVE GRAB |
| | BARS PROVIDED ON THREE SIDES IN ROLL IN SHOWERS WITHOUT |
| | SHEETS PER THE FAC SEC.608.3.2. SPACING FROM ADJACENT |
| | WALLS SHALL COMPLY WITH FAC SEC.608.3.2. |
| | 8) SHT. P0.1 - SIZE ALL SECTIONS OF THE VENTING SYSTEM |
| | ON THE SANITARY RISER. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1.2ND REQUEST. YOUR RESPONSE REFERS TO THE |
| | ARCHITECTURAL PAGES WHICH ARE ELEVATION DETAILS.?? |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |