Plan Review Notes
Plan Review Notes For Permit 15010129
Permit Number 15010129
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-21 12:49:321) SHT. CVR - PLBG. FIXTURES REQD. ALTHOUGH THE MINIMUM
 NUMBER OF FIXTURES HAS BEEN MET, PLEASE CORRECT THE
 REQUIRED FIXTURE COUNT. PER TABLE 403.1 OF THE 2010 FL.
 PLBG. CODE, 3 WATER CLOSETS ARE REQUIRED EACH FOR MALES
 AND FEMALES, NOT 2 EACH AS SHOWN.
 2) SINKS AND LAVATORIES SHALL COMPLY W/ 2010 FL.
 ACCESSIBILITY CODE. SEC606.1 & 606.3. THE FRONT OF THE
 HIGHER OF THE RIM OR COUNTER SURFACE SHALL BE A MAX. OF
 34 INCHES ABOVE THE FINISH FLOOR.
 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S
 SPECS/INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER
 FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 4) SUBMIT ENLARGED TOILET ROOM PLANS AND ELEVATION
 DETAILS SHOWING FULL COMPLIANCE WITH THE 2010 FAC.
 5) ONE OF THE URINALS SHALL BE HANDICAP ACCESSIBLE PER
 THE FAC SEC.213.3.3. SUBMIT AN ELEVATION DETAIL AND
 SHOW THE CLEAR FLOOR SPACE ON THE PLAN PER THE 2010 FAC
 305 & 605.
 6) SUBMIT AN ELEVATION DETAIL & ENLARGED PLAN FOR
 HANDICAP ACCESSIBLE SHOWER. SHOW THE DIMENSIONS OF THE
 SHOWER (LXW) AND COMPLIANCE WITH FAC SEC.608.
 7) DRINKING FOUNTAINS SHALL COMPLY WITH FAC SEC.211 &
 306. SHOW THE KNEE & TOE CLEARANCES ON THE PLAN.
 8) SIZE ALL SECTIONS OF THE VENTS ON THE SANITARY
 RISERS ON SHT.P0.1.
 9) A VACUUM RELIEF VALVE IS REQD. ON THE 30 GAL. WATER
 HEATER PER THE 2010 FPC SEC.504.2. THE PLAN SHOWS A
 VACUUM BREAKER WHICH IS NOT THE SAME.
 10) PLEASE CLARIFY WHY THERE IS A SHOWER STALL IN THE
 MEN'S RESTROOM #122 AND NOT ONE IN THE WOMEN'S.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR