| 2015-01-21 12:49:32 | 1) SHT. CVR - PLBG. FIXTURES REQD. ALTHOUGH THE MINIMUM |
| | NUMBER OF FIXTURES HAS BEEN MET, PLEASE CORRECT THE |
| | REQUIRED FIXTURE COUNT. PER TABLE 403.1 OF THE 2010 FL. |
| | PLBG. CODE, 3 WATER CLOSETS ARE REQUIRED EACH FOR MALES |
| | AND FEMALES, NOT 2 EACH AS SHOWN. |
| | 2) SINKS AND LAVATORIES SHALL COMPLY W/ 2010 FL. |
| | ACCESSIBILITY CODE. SEC606.1 & 606.3. THE FRONT OF THE |
| | HIGHER OF THE RIM OR COUNTER SURFACE SHALL BE A MAX. OF |
| | 34 INCHES ABOVE THE FINISH FLOOR. |
| | 3) SUBMIT 2 COPIES OF THE MANUFACTURER'S |
| | SPECS/INSTALLATION MANUAL FOR THE TANKLESS WATER HEATER |
| | FOR REVIEW. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 4) SUBMIT ENLARGED TOILET ROOM PLANS AND ELEVATION |
| | DETAILS SHOWING FULL COMPLIANCE WITH THE 2010 FAC. |
| | 5) ONE OF THE URINALS SHALL BE HANDICAP ACCESSIBLE PER |
| | THE FAC SEC.213.3.3. SUBMIT AN ELEVATION DETAIL AND |
| | SHOW THE CLEAR FLOOR SPACE ON THE PLAN PER THE 2010 FAC |
| | 305 & 605. |
| | 6) SUBMIT AN ELEVATION DETAIL & ENLARGED PLAN FOR |
| | HANDICAP ACCESSIBLE SHOWER. SHOW THE DIMENSIONS OF THE |
| | SHOWER (LXW) AND COMPLIANCE WITH FAC SEC.608. |
| | 7) DRINKING FOUNTAINS SHALL COMPLY WITH FAC SEC.211 & |
| | 306. SHOW THE KNEE & TOE CLEARANCES ON THE PLAN. |
| | 8) SIZE ALL SECTIONS OF THE VENTS ON THE SANITARY |
| | RISERS ON SHT.P0.1. |
| | 9) A VACUUM RELIEF VALVE IS REQD. ON THE 30 GAL. WATER |
| | HEATER PER THE 2010 FPC SEC.504.2. THE PLAN SHOWS A |
| | VACUUM BREAKER WHICH IS NOT THE SAME. |
| | 10) PLEASE CLARIFY WHY THERE IS A SHOWER STALL IN THE |
| | MEN'S RESTROOM #122 AND NOT ONE IN THE WOMEN'S. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |