2015-01-21 14:27:12PLAN DENIED
 1) PROVIDE NUMBERS ON RELOCATED AIR HANDLERS.
 PER SECTION 304.12 AREA SERVED 2010 FBC (M)
 2) SHOW WHERE 20 IN. SPIRAL DUCT IS GOING ON
 4 TON RELOCATED AIR HANDLER 107 FBC
 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE
 403.3 FBC (M) 2010
 4) PROVIDE ENERGY CALCULATIONS PER SECTION
 503.2.1 CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE.
  