| Plan Review Notes For Permit 15010129 |
| Permit Number |
15010129 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-21 14:27:12 | PLAN DENIED | | | 1) PROVIDE NUMBERS ON RELOCATED AIR HANDLERS. | | | PER SECTION 304.12 AREA SERVED 2010 FBC (M) | | | 2) SHOW WHERE 20 IN. SPIRAL DUCT IS GOING ON | | | 4 TON RELOCATED AIR HANDLER 107 FBC | | | 3) PROVIDE FRESH AIR CALCULATIONS PER TABLE | | | 403.3 FBC (M) 2010 | | | 4) PROVIDE ENERGY CALCULATIONS PER SECTION | | | 503.2.1 CALCULATION OF HEATING AND COOLING | | | 2010 FLORIDA ENERGY CODE. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|