Plan Review Notes
Plan Review Notes For Permit 15010129
Permit Number 15010129
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-20 08:57:37BUILDING PLAN REVIEW
 PERMIT: 15010129
 ADD: 2581 METROCENTRE BLVD. SUITE # 3 & 6
 CONT: J. J. MORLEY ENTERPRISES, INC.
 TEL: (561)843-5325
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN 20/2015
 ACTION: DENIED
  
 1) SHEET A-1.0 INDICATES THE USE OF A BREAK AREA, WITH
 A 2 BOWEL SINK, PLEASE PROVIDE COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE: 606 LAVATORIES AND SINKS606.1
 GENERAL. LAVATORIES AND SINKS SHALL COMPLY WITH 606.
  
 1A) 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 1B) 606.3 HEIGHT. LAVATORIES AND SINKS SHALL BE
 INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR
 COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
  
 1C) 606.4 FAUCETS. CONTROLS FOR FAUCETS SHALL COMPLY
 WITH 309. HAND-OPERATED METERING FAUCETS SHALL REMAIN
 OPEN FOR 10 SECONDS MINIMUM.
  
 1D) 606.5 EXPOSED PIPES AND SURFACES. WATER SUPPLY AND
 DRAIN PIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES AND SINKS.
  
 2) SHEET A-1.0 NOTE 18 INDICATES THE USE OF A MICROWAVE
 IN A DRAWER, PLEASE SHOW COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 309 OPERABLE PARTS
  
 2A) 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH
 309.
  
 2B) 309.2 CLEAR FLOOR SPACE. A CLEAR FLOOR OR GROUND
 SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
  
 2C) 309.3 HEIGHT. OPERABLE PARTS SHALL BE PLACED WITHIN
 ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308.
  
 2D) 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE
 WITH ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 3) SHEET A-1.0 NOTE # 7 INDICATES A NEW EXTERIOR DOOR
 OPENING. PLEASE PROVIDE THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 3.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 3.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 3.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 3.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 3.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 4) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 107.2.4
 EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL
 BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN
 SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH THIS
 CODE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676