 PROJECT: BENITZ BUILDING SITE LIGHTING
 PERMIT#: 15010121
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE BRANCH CIRCUITRY DETAILS INDICATING THE
 ELECTRICAL PANEL, CIRCUIT NUMBER AND CALCULATED LOAD OF
 THE CIRCUIT FEEDING SITE LIGHTING.
  
 2) PROVIDE THE METHOD OF COMPLIANCE WITH THE FBC-ENEGY
 SECTION 505. LIGHTING SHALL HAVE AUTOMATIC CONTROLS
 CAPABLE OF TURNING OFF EXTERIOR LIGHTING WHEN
 SUFFICIENT DAYLIGHT IS AVAILABLE OR WHEN THE LIGHTING
 IS NOT REQUIRED DURING NIGHTTIME HOURS.
  
 3) PROVIDE THE WIRING METHOD CONDUIT AND CONDUCTOR
 SIZES INDICATING THE CIRCUIT NUMBER(S) ON THE SITE
 PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  