| Notes |
| Date |
Text |
| 2015-02-19 12:16:26 | PLAN DENIED | | | PROVIDE ENGINEERING FOR THE EXHAUST FAN CURB | | | AND SUPPLY FAN CURB SHOWING CURB TO ROOF | | | TIEDOWN. PROVIDE TYPE, SIZE AND SPACING | | | OF THE ANCHOR. PROVIDE A DETAIL ON THE FANS TIE DOWN TO | | | CURB. PER SECTION 301.12 WIND RESISTANCE | | | 2010 FBC (M) | | | 2) SAFETY GUARD ON PAGE H.1 MUST EXTEND | | | 30 IN BEYOND END OF THE APPLIANCE. | | | PER SECTION 304.11 GUARDS 2010 FBC (M) | | | 3) PROVIDE TWO SETS OF PLANS ONLY ONE SUBMITTED | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|