| Date |
Text |
| 2015-01-29 18:23:18 | REVISION SECOND BUILDING REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | *****PLEASE REMOVE THE NAME OF JULIO GOMEZ, PERMIT # |
| | 14-120371 AND PHONE NUMBER FROM SHEETS S-1 AND S-2 |
| | SUBMITTED. THIS INFORMATION IS NOT PART OF THE |
| | CONSTRUCTION DRAWINGS AND I AM NOT THE DESIGNER. |
| | |
| | 1- REVISE PROJECT ADDRESS NUMBER IN ALL SHEETS. THE |
| | CORRECT ADDRESS NUMBER IS 5615 S. FLAGLER DR. NOT 5616 |
| | S. FLAGLER. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 2- SHEET A-2: REVISE THE DESIGN DATA. THIS BUILDING IS |
| | LOCATED IN EXPOSURE "D" NOT "C". AND REVISE THE DESIGN |
| | PRESSURES ACCORDINGLY. SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 3- TERRACE GUARDRAIL: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE LOADS |
| | OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. THERE IS NOT |
| | SPECS FOR POSTS AND CONNECTIONS AND GUARDRAIL SPECS AND |
| | CONNECTIONS. ALSO, PROVIDE INFORMATION SHOWING |
| | COMPLIANCE WITH THE REQUIREMENTS OF SEC. R312 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) THE UNDERLAYMENT SPECIFIED ON A/S-2 SECTION ON SHEET |
| | S-2. (UNDERLAYMENT PRODUCT APPROVAL WAS REQUESTED ON |
| | PREVIOUS CHECKLIST. THIS ITEM WAS NOT ADDRESSED). |
| | NOTE: PRODUCT APPROVAL NEED TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY R301 OF 2010 FBC-RESIDENTIAL AND |
| | MUST BE COMPATIBLE FOR THE PROPOSED TERRACE ASSEMBLY. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ABOVE PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- SHEET S-1: |
| | A) PROVIDE COMPLETE PRE-ENGINEERED FLOOR JOIST PACKAGE |
| | SHOWING CONFORMANCE WITH THE TERRACE LOADS SPECIFIED BY |
| | THE ENGINEER ( DEAD LOAD 100 LBS PSF AND LIVE LOAD 125 |
| | LBS PSF). SEC. 107.2.1.3 OF CITY AMENDMENTS TO FBC. |
| | |
| | B) SIZES OF FOOTINGS SHOWN ON THE FOUNDATION SCHEDULE |
| | ARE NOT CLEAR. FOR EXAMPLE FOOTING P1 IS 42" D X 42" W |
| | ?????. AND WHERE ARE P1 AND P2 LOCATED ON THE |
| | FOUNDATION PLAN?. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) ORIGINAL APPROVED PLANS WERE DESIGNED BASED ON THE |
| | SPECIFIC TYPE OF SOIL ENCOUNTERED IN THIS AREA. NEW |
| | ENGINEER OF RECORD TO ACKNOWLEDGE IN WRITING THAT |
| | PROPOSED FOUNDATION DESIGN IS BASED ON THOSE SPECIFIC |
| | SOIL CONDITIONS . SEC. 107.2.1.3 CITY |
| | AMENDMENTS.(REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | D) DESIGN SPECIFICATIONS NOTE #2 AND DESIGN CRITERIA AT |
| | THE BOTTOM LEFT OF THE SAME SHEET DOESN'T MATCH. REVISE |
| | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | E) HOW ARE THE LVL BEAMS ANCHORED TO THE COLUMNS? SEC. |
| | R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | F) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | KNEE WALLS?. SEC. R301.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | G) REVISE SIZE AND NUMBER OF FASTENERS REQUIRED FOR THE |
| | SIMPSON LUS-210. ALSO, REVISE INFORMATION ON SECTION |
| | A/S2. SEE SIMPSON PRODUCT APPROVAL FOR CORRECT SIZE AND |
| | NUMBER. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 7- SCOPE OF WORK SUBMITTED WITH THIS REVISION INCLUDES |
| | A LOT MORE WORK THAN THE SPECIFIED ON THE ORIGINAL |
| | APPROVED PLANS. UPDATE VALUATION TO INCLUDE ALL LABOR, |
| | MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND ALL |
| | DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACT THAT |
| | INCLUDES ALL SPECIFIED WORK. (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | 8- THERE IS A REVISION FEE OF $154.50 FOR THIS |
| | SUBMITTAL. (2 NEW DRAWINGS AND ONE NEW NOA). |
| | |
| | ***NOTE: THERE IS AN EXISTING FIREPLACE BETWEEN THE |
| | FIRST FLOOR AND THE TERRACE. THERE IS NO INFORMATION |
| | PROVIDED SHOWING THAT THE PROPOSED CONSTRUCTION WILL |
| | NOT CREATE A FIRE HAZARD. ADDITONAL INFORMATION MAY BE |
| | REQUIRED. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |