Plan Review Notes
Plan Review Notes For Permit 14120917
Permit Number 14120917
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-14 10:52:041ST REVIEW: FBC 2010
  
 THE NEWLY ADDED OUTDOOR KITCHEN DOES NOT APPEAR TO
 COMPLY WITH THE FOLLOWING SECTIONS:
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 210.52 (C) - KITCHEN COUNTER TOP RECEPTACLE SPACING
 (C) COUNTERTOPS. IN KITCHENS, PANTRIES, BREAKFAST
 ROOMS,DINING ROOMS, AND SIMILAR AREAS OF DWELLING
 UNITS, RECEPTACLE
 OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.52(C)(1) THROUGH (C)(5).
 REVISE ACCORDINGLY.
  