| Notes |
| Date |
Text |
| 2015-01-14 10:52:04 | 1ST REVIEW: FBC 2010 | | | | | | THE NEWLY ADDED OUTDOOR KITCHEN DOES NOT APPEAR TO | | | COMPLY WITH THE FOLLOWING SECTIONS: | | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | | BRANCH CIRCUITS. | | | NEC 210.52 (C) - KITCHEN COUNTER TOP RECEPTACLE SPACING | | | (C) COUNTERTOPS. IN KITCHENS, PANTRIES, BREAKFAST | | | ROOMS,DINING ROOMS, AND SIMILAR AREAS OF DWELLING | | | UNITS, RECEPTACLE | | | OUTLETS FOR COUNTERTOP SPACES SHALL BE INSTALLED IN | | | ACCORDANCE WITH 210.52(C)(1) THROUGH (C)(5). | | | REVISE ACCORDINGLY. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | |
|