| 2015-01-08 10:11:14 | RESIDENTIAL (R3) REVISION BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- REVISE PROJECT ADDRESS NUMBER IN ALL SHEETS. THE |
| | CORRECT ADDRESS NUMBER IS 5615 S. FLAGLER DR. NOT 5616 |
| | S. FLAGLER. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- SHEET A-2: REVISE THE DESIGN DATA. THIS BUILDING IS |
| | LOCATED IN EXPOSURE "D" NOT "C". AND REVISE THE DESIGN |
| | PRESSURES ACCORDINGLY. SEC. R301.2.1.4.3 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- TERRACE GUARDRAIL: PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE LOADS |
| | OF TABLE R301.5 OF 2010 FBC-RESIDENTIAL. THERE IS NOT |
| | SPECS FOR POSTS AND CONNECTIONS AND GUARDRAIL SPECS AND |
| | CONNECTIONS. ALSO, PROVIDE INFORMATION SHOWING |
| | COMPLIANCE WITH THE REQUIREMENTS OF SEC. R312 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| | TERRACE FLOORING ASSEMBLY AS REQUIRED BY SEC. R903.1. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) TERRACE UNDERLAYMENT SPECIFIED ON ITEM #4 ABOVE. |
| | |
| | B) ALL STRUCTURAL CONNECTORS SPECIFIED ON ALL FRAMING |
| | PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR |
| | LIST FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE |
| | SPECIFIED CONNECTOR IN ALL PLANS AND DETAILS. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS, INCLUDING THE FRENCH DOOR. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 7- A) NO FOUNDATION PLAN WAS PROVIDED. PROVIDE COMPLETE |
| | FOUNDATION PLAN SHOWING COMPLIANCE WITH SEC. R401.2 OF |
| | 2010 FBC-RESIDENTIAL. |
| | |
| | B) ORIGINAL APPROVED PLANS WERE DESIGNED BASED ON THE |
| | SPECIFIC TYPE OF SOIL ENCOUNTERED IN THIS AREA AND |
| | BECAUSE THIS PROPERTY IS LOCATED IN FLOOD ZONE A5. NEW |
| | ENGINEER OF RECORD TO ACKNOWLEDGE IN WRITING THAT |
| | PROPOSED FOUNDATION DESIGN IS BASED ON THOSE SPECIFIC |
| | SOIL CONDITIONS. SEC. 107.2.1.3 CITY AMENDMENTS. |
| | |
| | 8- PROVIDE COMPLETE FRAMING PLANS, SPECIFICATIONS AND |
| | DETAILS/SECTIONS FOR THE NEW TERRACE. NO STRUCTURAL |
| | INFORMATION WAS PROVIDED. SEC. R501.2 OF 2010 |
| | FBC-RESIDENTIAL. |
| | ***NOTE: INCLUDE DETAILS AND SPECIFICATIONS FOR THE |
| | CEILING ASSEMBLY BELOW THE TERRACE. |
| | |
| | 9- SCOPE OF WORK SUBMITTED WITH THIS REVISION INCLUDES |
| | A LOT MORE WORK THAN THE SPECIFIED ON THE ORIGINAL |
| | APPROVED PLANS. UPDATE VALUATION TO INCLUDE ALL LABOR, |
| | MATERIALS, CONTRACTOR'S OVERHEAD AND PROFIT AND ALL |
| | DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. PROVIDE COPY OF SIGNED CONTRACT THAT |
| | INCLUDES ALL SPECIFIED WORK. |
| | |
| | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |