| Plan Review Notes For Permit 14120915 |
| Permit Number |
14120915 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2015-10-08 11:36:22 | ELECTRICAL PROVISO FOR PERMIT 14120915 | | | IN ORDER TO BRING THE UNPERMITTED KITCHEN INTO | | | COMPLIANCE, THE MINIMUM REQUIRED OUTLETS SHALL BE IN | | | PLACE. THE DRAWING SUBMITTED FAILS TO INDICATE; | | | THEREFORE CORRECTIONS ARE REQUIRED. FURTHERMORE THE | | | PANEL PERMITTED OR NOT SHALL ALSO BE ACCORDING TO | | | MINIMUM CODE STANDARDS; THUS REQUIRING THAT THERE BE A | | | DISCONNECT AS INDICATED BY NEC 230.70(A)(1). SEE NEC | | | 230.6 FOR FURTHER DETAILS. | | | |
|