| 2015-03-31 14:16:15 | 3/31/2015 |
| | PROJECT: LJUBO 827 BRIGGS ST |
| | PERMIT#: 14100826 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE ELECTRICAL RISER DIAGRAM TO INDICATE THE |
| | FOLLOWING: |
| | A MAIN DISCONNECTING MEANS AS REQUIRED BY NEC 230.70 |
| | SIZES OF MAIN DISCONNECT, SERVICE ENTRANCE, FEEDERS, |
| | PANEL, AND GROUNDING ELECTRODE SYSTEM. NEC 215.5, |
| | 250.50 |
| | |
| | 2) LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN |
| | PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN |
| | ACCORDANCE WITH EITHER 220.12 OR 220.14, AS APPLICABLE. |
| | NEC 220.16(2) |
| | |
| | 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| | SPECIFIC PURPOSE OR USE. NEC 408.4 |
| | |
| | 3) INDICATE CIRCUITS ON THE FLOORPLAN FOR CLARITY. WPB |
| | AMENDMENTS TO FBC 107.3.2 |
| | |
| | 4) AT LEAST ONE GFI RECEPTACLE OUTLET SHALL BE |
| | INSTALLED AT EACH PENINSULAR COUNTERTOP SPACE. NEC |
| | 210.52(C)(3) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |