| 2015-05-06 10:24:23 | 1) THIS BUILDING IS CLASSIFIED AS AN R-2 OCCUPANCY ON |
| | SHT. G001 (001) AND IS EQUIPPED WITH AN ELEVATOR |
| | THEREFORE ALL THE RESIDENTIAL UNITS ON ALL THE FLOORS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FEDERAL FAIR |
| | HOUSING ACT AND SEC. 233 OF THE 2010 FL. ACCESSIBILITY |
| | CODE.UNDER THE HEADING "FBC 2010 ACCESSIBILITY |
| | ACCESSIBLE UNITS" THERE IS A REFERENCE TO CODE SECTION |
| | 11-9.1.4. THERE IS NO SUCH CODE SECTION IN THE 2010 |
| | FBC.HOW ARE YOU ARRIVING TO THE FACT THAT ONLY 5% OF |
| | THE UNITS HAVE TO COMPLY WITH HANDICAP REQUIREMENTS? |
| | CALRIFY. |
| | 2) THE APPLICATION SUBMITTED WITH THESE PLANS STATE |
| | "FOUNDATION ONLY" YET THE PLANS ARE FULL SETS FOR PHASE |
| | I & PHASE II. THE APPLICATION DOES NOT STATE IF THE |
| | FOUNDATION PLAN IS FOR BOTH PHASES OR JUST ONE. |
| | CLARIFY. |
| | 3) SHT.G101 - CLARIFY HOW YOU ARRIVED AT THE REQD. |
| | FIXTURES FOR THE GROUP A-1, A-2, A-3 OCCUPANCIES. I |
| | CAME UP WITH SLIGHTLY DIFFERENT DECIMAL EQUIVQLENTS. |
| | WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 4)SHT.G101 - DEFINE THE ASTERISKS ON THE PLUMBING |
| | FIXTURE TABLE. I DO NOT SEE ANY FOOTNOTES. CLARIFY. |
| | 5) SHT. AS 106 - THE WATER SUPPLY FOR THE FOUNTAIN |
| | SHALL BE EQUIPPED WITH A BACKFLOW PREVENTION DEVICE PER |
| | 2010 FPC SEC.608.1. |
| | 6) SHT. AS 109 ( DETAIL #1 ) THE SINK SHALL COMPLY |
| | W/THE FAIR HOUSING ACT FOR ACCESSIBLE AND USABLE PUBLIC |
| | AND COMMON USE AREAS PER CFR 100.205. |
| | 7) SHT. AS 106 - THE WATER SUPPLY FOR THE FOUNTAIN |
| | SHALL BE EQUIPPED WITH A BACKFLOW PREVENTION DEVICE PER |
| | 2010 FPC SEC.608.1. |
| | 8) SHT. AS109 - FLOOR DRAINS ARE SHOWN IN THE POOL |
| | SERVICE AREA. INDICATE IF THEY ARE CONNECTED TO THE |
| | STORM OR SANITARY SYSTEM. |
| | 9) SUBMIT COMPLETE DETAILS FOR THE EMERGENCY GENERATOR. |
| | SUBMIT MANUFACTURER'S SPECS, FUEL AND FUEL PIPING |
| | DETAILS,GENERATOR EXHAUST, ETC. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | 10) THE SINK IN THE ART STUDIO #124 ANF THE BREAK ROOM |
| | SINK #167 SHALL COMPLY W/THE FAIR HOUSING ACT FOR |
| | ACCESSIBLE AND USABLE PUBLIC AND COMMON USE AREAS PER |
| | CFR 100.205. |
| | 11) SHT. A-400 SHOW THE LENGTH AND WIDTH DIMENSIONS OF |
| | THE REINFORCING FOR THE GRAB BARS FOR THE SHOWERS, |
| | TUBS, & WATER CLOSETS. ALSO, SHOW THE MINIMUM AND |
| | MAXIMUM HEIGHT DIMENSIONS FOR THE LOCATION OF |
| | REINFORCEMENT. COMPLY WITH CFR 100.205 (6) & ANSI |
| | A117.1. |
| | 12) SHT. A401B - SHOW THE CLEAR INSIDE DIMENSIONS (L X |
| | W) OF THE SHOWER. A 30 X 48 INCH CLEAR FLOOR SPACE |
| | SHALL BE PROVIDED AT SHOWER STALLS, PARALLEL TO THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL. |
| | 13) SHT. A403 SHOW THE HEIGHTS OF THE CABINETS, GRAB |
| | BARS, ETC. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 14) INDICATE ON THE PLANS THE DESIGN SPECIFICATION (A |
| | OR B) BEING USED FOR THE DESIGN OF THE USABLE BATHROOMS |
| | .SPECIFICATION A APPLIES TO ALL BATHROOMS IN THE |
| | COVERED DWELLING UNIT AND ALL FIXTURES IN THOSE |
| | BATHROOMS MUST BE USABLE . SPECIFICATION B APPLIES TO |
| | ONE BATHROOM AND ONLY ONE OF EACH TYPE OF FIXTURE MUST |
| | BE USABLE; ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT |
| | ONLY FROM MANEUVERING AND CLEAR FLOOR SPACE AT |
| | FIXTURES. |
| | 15) SHT. A451 SHOW THE LENGTH OF THE AMBULATORY TOILET |
| | STALLS IN THE MEN'S & WOMEN'S RESTROOMS. COMPLY WITH |
| | THE 2010 FAC SEC. 604.8.2.1. DOORS SHALL NOT SWING INTO |
| | THE MINIMUM REQUIRED COMPARTMENT AREA PER SEC. |
| | 604.8.2./ANSI A117.1. |
| | 16) SHT. A452 GRAB BARS ARE REQUIRED IN THE ACCESSIBLE |
| | SHOWER IN THE ACCESSIBLE CHANGING ROOM. FAC SEC. 608.3 |
| | & 609.4. A SEAT SHALL ALSO BE PROVIDED PER FAC |
| | SEC.608.4. |
| | 17) SHT.A452 THE ACCESSIBLE CHANGING ROOM IS LISTED AS |
| | #149 ON THE PLAN VIEW IN DETAIL #014 AND AS #142 & 143 |
| | ON THE ELEVATION DETAILS. IS THIS A TYPO? CLARIFY. |
| | 18) SHT. A506 INDICATE ON THE PLAN IF THE FIREPLACE IS |
| | WOOD OR GAS BURNING. IF GAS, SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE UNIT AND SHOW IT ON THE GAS |
| | RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 19) SHT.A510 DETAIL #2 SHOW THE REQUIRED CLEARANCES FOR |
| | THE ACCESSIBLE LAVATORY PER THE FAC SEC.306. |
| | 20) PLACE THE PLANS IN ORDER AS THEY ARE LISTED IN THE |
| | INDEX SHEET. TIME IS WASTED SEARCHING FOR THE LOCATION |
| | OF PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 21) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL THE |
| | GAS EQUIPMENT & APPLIANCES. APPLIANCES & EQUIPMENT |
| | SHALL BE LISTED PER THE 2010 FBC-FUEL GAS CODE SEC. |
| | 301.3. MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ALL |
| | APPLIANCES/EQUIPMENT SHALL BE ON THE JOBSITE PER 2010 |
| | FBC-FUEL GAS CODE SEC.305.1. |
| | 22) FOOD SERVICE DRAWINGS. SUBMIT MANUFACTURING |
| | SPECIFICATIONS FOR ALL GAS EQUIPMENT. EQUIPMENT SHALL |
| | BE LISTED AND LABELED PER FBC-FUEL GAS SEC. 301.3. |
| | 23) FOOD SERVICE EQUIPMENT SHALL BE NSF APPROVED .2010 |
| | FBC-PLUMBING SEC.409. |
| | 24) SHT. FS-4 - PLUMBING CONNECTION DETAILS FOR ITEMS # |
| | 36,38,140. THERE IS NO LEGEND FOR THE ITEM #140 ON THE |
| | FS DRAWINGS. CLARIFY. |
| | 25) SHT. P105 (2-125) PHASE II THE PLAN SHOWS A 4" |
| | RAINWATER LEADER (RL 13) WITH 1535 SQ. FEET DRAINING |
| | INTO IT. THE MAXIMUM SQUARE FOOTAGE IS 1504 PER |
| | FBC-PLUMBING TABLE 1106.3.SEE DRAIN NEAR GRIDLINE |
| | G/2.8. |
| | 26) PROVIDE A SCUPPER DETAIL. SCUPPERS SHALL NOT HAVE |
| | AN OPENING DIMENSION LESS THAN 4 INCHES. 2010- FBC- |
| | PLUMBING SEC. 1107.3. SCUPPERS SHALL COMPLY WITH 2010 |
| | FBC SEC. 1503.4.2.1. |
| | 27) SHT.P100B (2-120) DOES NOT CORRELATE WITH THE |
| | SANITARY RISER ON SHT. P401 (2-128) AS TO THE LAYOUT. |
| | BRANCHES ARE SHOWN ON P100B THAT ARE NOT ON P401. ALSO |
| | SANITARY RISER #33 DOES NOT APPEAR TO CONNECT TO THE |
| | BUILDING DRAIN. WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 28) SHT.P401 (2-128) THERE ARE NO CONTINUATION POINTS |
| | SHOWN FOR THE STACK VENTS OR BRANCH VENTS. CLARIFY. I |
| | HAVE IDENTIFIED THESE AREAS WITH A MARKUP. |
| | 29) SHT. P100B (2-120) THERE IS A CD RISER & A SANITARY |
| | RISER THAT IS NOT NUMBERED. CLARIFY.IT HAS BEEN |
| | IDENTIFIED THEM WITH A MARKUP. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | 30) SHT.P101B (2-121) ROOM #133.THERE IS A CD RISER |
| | THAT IS NOT NUMBERED.CLARIFY. IT HAS BEEN IDENTIFIED |
| | WITH A MARKUP. |
| | 31) SHT. P102B (2-122) THERE IS A SANITARY RISER THAT |
| | IS NOT IDENTIFIED BY A NUMBER. SEE GRIDLINE F/4.2. IT |
| | IS IDENTIFIED WITH A MARKUP. CLARIFY. THIS OCCURS ON |
| | ALL LEVELS. |
| | 31) SHT. P402 (2-129) WHERE IS SANITARY RISER #31? |
| | CLARIFY. |
| | 32) SHT. P402 (2-129) SANITARY RISER #29 WC-1 APPEARS |
| | TO BE DRAINING INTO A 2 INCH LINE. IT APPEARS AS THOUGH |
| | WC-1 MAY BE MISLABELED. IF IT IS A WATER CLOSET THEN |
| | THE 3 " VENT STACK NEEDS TO BE INCREASED TO 4 INCHES |
| | PER 2010 FPC TABLE 916.1. CLARIFY. |
| | 33) SHT. P402 (2-129) SANITARY RISER #29 DOES NOT |
| | COMPLY WITH FPC 2010 SEC. 909.1 FOR THE TYPE OF |
| | FIXTURES PERMITTED ON A HORIZONTAL WET VENT. ALSO, SIZE |
| | THE HORIZONTAL DRAIN BETWEEN WC-1 AND OB-1 ON THE |
| | RISER. |
| | 34) SHT. P402 (2-129) SANITARY RISERS #28 AND #31 ARE |
| | NOT SHOWN ON THE PLAN. CLARIFY. |
| | 35) SHT. P403 (2-130) & P201B (2-126) IDENTIFY THE |
| | OTHER TWO WATER MAINS AND PROVIDE PAGE NUMBER FOR |
| | CONTINUATION POINT. PROVIDE IDENTIFICATION LEGEND FOR |
| | THE MAINS. WPB AMEND. TO 2010 FBC SEC. 107.2.1., |
| | 107.3.5.1.3. |
| | 36) SHT. P201B (2-126) OB-1 AND WC-1 (UNIT D2 # 102) - |
| | THE SYMBOL IS SHOWN ON THE PLAN VIEW BUT THERE IS NO |
| | WATER PIPING SHOWN TO THE FIXTURE. CLARIFY. |
| | 37) SHT. P301 (2-127) - EXPLAIN HOW HALF OF UNIT A1C |
| | CAN BE LOCATED IN PHASE I AND THE OTHER HALF IN PHASE |
| | II. WHAT OCCURS IF BOTH PHASES ARE NOT BUILT AT THE |
| | SAME TIME? |
| | 38) IT IS EXTREMELY DIFFICULT TO FIGURE WHICH |
| | CONDENSATE, SANITARY AND WATER RISER APPLY TO WHICH |
| | MODEL UNITS. SHOW THE LOCATION AND IDENTIFY THE RISERS |
| | ON THE ENLARGED FLOOR PLANS FOR THE UNITS. WPB AMEND. |
| | TO 2010 FBC SEC.107.2.1, 107.3.5.1.3. |
| | 39) SHT. P501 (2-135) SHOW THE SIZE OF THE COPPER DWV |
| | LINE FROM THE WASHING MACHINE. THE MIN. SIZE OF THE |
| | TRAP & STANDPIPE SHALL BE 2" AND SHALL CONNECT TO A |
| | BRANCH DRAIN OR DRAINAGE STACK THAT IS A MINIMUM OF 3 |
| | INCHES. FPC SEC.406.3. SEE ALSO SHT. P404. |
| | 40) SHT. P404 (2-131) THE SIZE OF THE WATER RISERS DO |
| | NOT MATCH FROM THE 9TH TO THE 10TH FLOOR. REFER TO |
| | RISESRS # 24, 26, 27,29,30, & 31. CLARIFY. |
| | 41) SHT. P404 (2-131) WATER RISER #28 IS NOT SHOWN ON |
| | THE PLAN. CLARIFY. |
| | 42) 42) SHT.P105 (2-125) SUBMIT DETAILS FOR SECONDARY |
| | (EMERGENCY) ROOF DRAINAGE PER 2010 FBC-PLUMBING, |
| | SECS.1107.1, 1107.2, 1107.3 AND 2010 FBC-BUILDING, |
| | SECS. 1503.4.1, 1503.4.2.1. |
| | 43) SHT.P405 (2-132) INDICATE THE SLOPE OF ALL THE |
| | HORIZONTAL STORM DRAIN PIPING. COMPLY WITH 2010 |
| | FBC-PLUMBING TABLE 1106.3. |
| | COMMENTS ON THE STORM DRAIN SYSTEM ARE ASSUMING A 1% |
| | SLOPE ON THE PIPE. |
| | 44) SHT.P405 (2-132) IF THE SLOPE OF THE PIPE IS 1/8" |
| | UNIT VERTICAL IN 12 UNITS HORIZONTAL (1% SLOPE), THEN |
| | THE UNDERGROUND STORM DRAIN DOWNSTREAM OF RL/ 9 MUST BE |
| | 10", NOT 8". |
| | 45) SHT.P405 SIZE THE STORM DRAIN DOWNSTREAM OF RL/2. |
| | 46) SHT. P405 CHECK THE CALCULATIONS FOR THE TOTAL |
| | SQUARE FOOTAGE BEING DRAINED. MY CALCULATIONS ARRIVE AT |
| | 32,200 SQ. FT. |
| | 47) SHT.P407 (2-134) THE CONDENSATE RISER SHOWS 1/2" |
| | DRAINS FROM THE FAN COIL UNITS. THE MINIMUM SIZE DRAIN |
| | SHALL BE 3/4" I.D. PER FBC-PLBG., SEC.314.2.2 & TABLE |
| | 314.2.2. |
| | 48) SHT.P407 (2-134) IDENTIFY ALL THE CONDENSATE |
| | RISERS. (U/G, ROOF LEVEL, FAN COIL DETAILS) IT IS |
| | EXTREMELY DIFFICULT AND TIME CONSUMING TO TRY TO |
| | DETERMINE WHERE THESE RISERS ARE LOCATED. WPB AMEND. TO |
| | WPB SEC. 107.3.5.1.3. |
| | 49) THE CONDENSATE RISERS FOR THE FAN COILS SHOW A 3" |
| | FLOOR DRAIN DISCHARGING INTO THE RISER. WHAT IS |
| | DISCHARGING INTO THIS FLOOR DRAIN? |
| | 50) SHT.P407 (2-134) IDENTIFY THE PIECE OF EQUIPMENT |
| | SHOWN ON THE PLAN. WPB AMEND. TO 2010 FBC. 107.2.1. |
| | 51) SHT.P407 (2-134) SHOWS A 4" CONDENSATE DRAIN INTO |
| | THE SUMP AND A 4" DISCHARGE AND DETAIL #2 SHOWS A 1 " |
| | DISCHARGE. CLARIFY. |
| | 52) SHT. P501 (2-135)? SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS/INSTALL MANUAL FOR THE CONDENSATE WATER |
| | PUMP PACKAGE STSP-3. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. SHOW THE DIMENSIONS OF THE SUMP. |
| | 53) 53) SHT.P002 (261) SUBMIT MANUF. SPECS FOR THE OIL |
| | SMART SUMP PUMP. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 54) SHT. P003 (262) - CLEARLY SHOW THE ENTIRE LIMITS OF |
| | PHASE ONE AND PHASE TWO ON THE PLAN. |
| | 55) SHT. P003 (262) PLBG. KEYNOTE #3 STATES THE COOLING |
| | BASIN OVERFLOW TO SANITARY. COOLING TOWER WATER CANNOT |
| | DRAIN TO THE SANITARY PER CITY ORDINANCE 90-126 (5). |
| | 56) SHT. P501 (299) THE GREASE TRAP SHALL COMPLY WITH |
| | 2010 FPC SEC.1003.5.1 & 1003.5.2, 1003.5.3. SUBMIT |
| | SIZING CALCULATIONS FOR HE INTERCEPTOR IN ACCORDANCE |
| | WITH 2010 FPC. TABLE 1003.5.1. |
| | 57) SHT. P501 (299) & SHT. P003 (262) SIZE THE INLET |
| | AND OUTLET LINE FROM THE INTERCEPTORS. |
| | 58) SHT.P003 (262) SIZE THE 3 STORM LINES COMING FROM |
| | THE NEW RESIDENT BUILDING AND SIZE THE CDU LINE. |
| | 59) SHT. P003 - THE CONDENSATE DISCHARGE LINE IS SHOWN |
| | AS 2" ON THE CIVIL PLANS AND AS 4". CLARIFY. |
| | 60) THE COOLING TOWER SHALL COMPLY WITH NFPA 214. |
| | SUBMIT DETAILS. |
| | 61) SUBMIT MANUF. SPECS FOR THE PIPE WRAP FOR THE |
| | UNDERGROUND CONDENSATE PIPE. WPB AMEND. TO 2010 FBC |
| | SEC. 107.2.1. |
| | 62) INDICATE ON THE PLAN IF THE GENERATOR IS NEW OR |
| | EXISTING. IF NEW, SUBMIT SPECIFICATIONS FOR IT. |
| | 63) SHT. 101C (268) LABEL THE RAINWATER LEADER LOCATED |
| | IN THE CARTS ROOM #155, THE DINING ROOM AND HOSTESS |
| | ROOM #157. |
| | 64) SHT.P102A (269) LABEL THE CD RISER LOCATED IN ROOM |
| | #237 THAT GOES TO AREA MARKED ?OPEN TO BELOW. |
| | 65 ) SHT. 205C (102B) LABEL THE CD RISER FROM THE FCU |
| | IN ROOM NEXT TO TRASH ROOM . |
| | 66) SHT. P103A (271) IDENTIFY THE CD RISER IN COMMUNITY |
| | ROOM # 837. LABEL ALL THE CONDENSATE RISERS ON SHTS. |
| | P102A, P103A, 103B, ETC. |
| | 67) IDENTIFY ALL THE SHEETS FOR CONTINUATION OF THE |
| | MATCH LINES. THERE ARE NO REFERENCE SHEET NUMBERS AT |
| | THE MATCH LINES . |
| | 68) SUBMIT A LEGEND FOR IDENTIFICATION OF THE WATER |
| | MAINS AND WHAT THEY ARE. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 69) ROOF DRAINAGE INDICATE ON THE STORM RISER PLANS |
| | THAT THE SIZING OF THE STORM DRAINAGE INCLUDES 1/2 OF |
| | THE SQUARE FOOTAGE OF ANY VERTICAL (PARAPET) WALLS PER |
| | FBC-PLUMBING, SEC.1106.4. |
| | 70) SHT. P401A (285) ? THE ISOMETRIC SHOWS A FLAT DRY |
| | VENT BY SAN. RISER #1. THE SHOWER DOWNSTREAM OF STACK |
| | S/8 MUST BE LOCATED DOWNSTREAM A MINIMUM OF 10 PIPE |
| | DIAMETERS OF THE UPPER DRAINAGE STACK. IDENTIFY THE |
| | PLUMBING FIXTURE DOWNSTREAM OF STACK S/15. SEE ALSO |
| | FIXTURE S-1 DOWNSTREAM OF STACK S/16. SEE FPC |
| | SEC.704.3. |
| | 71) 71) SHT. P402 (287)SAN RISERS #1, #3, & # 6 DO NOT |
| | COMPLY WITH FPC SEC. 909 FOR ALLOWED FIXTURES ON A |
| | HORIZONTAL WET VENT. THE WASHING MACHINES AND S-2 ARE |
| | NOT FIXTURES IN A BATHROOM GROUP AND ARE NOT PERMITTED |
| | ON A WET VENT. ALSO, THE FIXTURE BT-1 IS NOT VENTED ON |
| | SAN. RISER #4. |
| | 72) SHT.P412 (297) SHOWS 3 " GAS DROPS TO THE WATER |
| | HEATERS AND SHT.502 (300) SHOWS 1 1/4" AND A 2" GAS |
| | LINE TO THE WATER HEATERS. CLARIFY. |
| | 73) SHT. P412 SHOWS THE LONGEST RUN AS 400 FT. BUT MY |
| | CALCULATIONS COME TO 498 FT. CLARIFY. |
| | 74) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS |
| | EQUIPMENT. ALL EQUIPMENT/APPLIANCES SHALL BE LISTED AND |
| | LABELED PER FBC-FUEL GAS SEC. 301.3. |
| | 75) SHT. P412 NATURAL GAS RISER DIAGRAM - IF THE |
| | LONGEST RUN IS CONFIRMED AT 498 FT. THEN THE PIPE SIZES |
| | OF THE FOLLOWING SECTIONS NEED TO BE REVISED AS |
| | FOLLOWS: PIPE SECTION I-J SHALL BE A MIN. OF 1 ??. |
| | SECTION H-I SHALL BE 3?. SECTION D-E SHALL BE 5? |
| | MINIMUM. A MAXIMUM OF 2110 CFH IS ALLOWED ON A 4" LINE |
| | AT ? PSI PER THE REFERENCED TABLE FROM NFPA. |
| | 76) SHT. P412 - INSTALLATION OF UNDERGROUND PIPING |
| | SHALL COMPLY WITH NFPA SEC.7.1.6.2 OR 2010 FBC -FUEL |
| | GAS, SEC.404.6.2. INDICATE TYPE OF PIPING TO BE USED. |
| | 77) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN |
| | ACCORDANCE WITH 2010 FBC - FUEL GAS SEC.304. SUBMIT |
| | DETAILS ON LOCATION AND TYPES OF VENTS, HEIGHT ABOVE |
| | ROOF, ETC. |
| | 78)SHT. P501 - SIZE ALL SECTIONS OF THE PIPING FOR THE |
| | DOMESTIC BOOSTER WATER PUMP, WATER SOFTENER AND |
| | PRESSURE REDUCING STATION. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | |