| 2015-08-07 12:04:18 | 4920 LORING DRIVE |
| | PERMIT #14120909 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | |
| | 2ND REVIEW |
| | SHEET G101: NO EXIT SIGNAGE PROVIDED FOR CORRIDOR |
| | ADJACENT TO CONFERENCE #112. |
| | |
| | SHEET G101: PROVIDE ADDITIONAL EXIT SIGN AT EAST END OF |
| | CORRIDOR #146A. ALSO DOOR APPEARS TO SERVE 51 PERSONS |
| | SO THE SWING WOULD NEED TO BE WITH THE FLOW OF TRAFFIC |
| | AND BE EQUIPPED WITH PANIC HARDWARE. |
| | |
| | REPEAT COMMENT -SHEET G001: UPDATE THE CODE LIST TO |
| | REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH |
| | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | SHEET A101 DOES NOT APPEAR TO BE UPDATED TO MATCH THE |
| | LIFE SAFETY PLAN. |
| | |
| | NOTE: THE COOKING GRILL LOCATED ON THE POOL DECK SHALL |
| | COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST 10 |
| | FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES PER |
| | NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED |
| | UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH |
| | NFPA 96. |
| | |
| | REPEAT COMMENT - SHEET FP402: FIRE PUMP SCHEDULE DOES |
| | NOT INDICATE A RATED PRESSURE OR HORSEPOWER RATING. THE |
| | ENGINEERING DOCUMENTS WILL BE REQUIRED TO DETERMINE IF |
| | PRESSURE REDUCING VALVES ARE NEEDED ON THE STANDPIPES |
| | AND SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL |
| | ALSO REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH |
| | DRAIN RISER AS SHOWN ON THE PLANS. |
| | |
| | REPEAT COMMENT - SHEET FP402: PER FBC SECTION403.3.2 |
| | WATER SUPPLY TO REQUIRED FIRE PUMPS - REQUIRED FIRE |
| | PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF |
| | TWO WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE |
| | SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION |
| | TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND |
| | THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS |
| | SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED |
| | FOR THE PUMPS TO OPERATE. |
| | |
| | |
| | PHASE 2 - FIRE DEPARTMENT REVIEW |
| | |
| | REPEAT COMMENT - SHEET G001: UPDATE THE CODE LIST TO |
| | REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE |
| | PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH |
| | NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. PER |
| | SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN OCCUPANCY |
| | TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY |
| | SHALL BE TREATED AS A MIXED OCCUPANCY. |
| | |
| | |
| | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| | 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |