| 2015-05-18 14:50:23 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 2010 FLORIDA BUILDING CODE |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | |
| | 1. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D) ALL PLANS |
| | FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A |
| | STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR |
| | ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS |
| | COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND |
| | THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY |
| | THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND |
| | CHAPTER 633. |
| | |
| | PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS |
| | TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF |
| | DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH |
| | SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY, |
| | PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH |
| | THE APPROPRIATE BOARD. |
| | |
| | 2. IT IS NOT CLEAR WHETHER THE NEW BUILDING WILL BE |
| | CONSIDERED AN ADDITION TO THE EXISTING BUILDING, ON THE |
| | SAME PARCEL, CONNECTED BY A WALKWAY, OR IF WILL BE |
| | TREATED AS A NEW BUILDING, SEPARATE PARCEL, OR NEW |
| | BUILDING, SAME PARCEL (WITH UNITY OF TITLE, SEE OTHER |
| | COMMENTS). |
| | |
| | IF THE TWO TOWERS ARE DESIGNED AS ONE BUILDING, |
| | DESIGNER TO REFERENCE FBC 2010 EXISTING BUILDING |
| | CHAPTER 10 (ADDITIONS) AS WELL AS METHOD OF COMPLIANCE |
| | FOR THE EXISTING BUILDING (SEE FBC 2010 EXISTING |
| | BUILDING 101.5). THIS IS REQUIRED IN ORDER TO ADDRESS |
| | ISSUES AS THEY ARISE EITHER IN THE FIELD OR IN PLAN. |
| | |
| | 3. CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES |
| | FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE |
| | I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF |
| | THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS |
| | ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE |
| | PARTIES, PLEASE CONTACT ME TO DISCUSS. |
| | |
| | THRESHOLD DOCUMENTS REQUIRED: |
| | |
| | SPECIAL INSPECTOR AGREEMENT |
| | RESUME AND COPIES OF LICENSES FOR SPECIAL INSPECTOR AND |
| | ALL ON SITE INSPECTORS |
| | RESUME AND COPIES OF LICENSES FOR CONTRACTOR, JOB |
| | SUPERINTENDENT AND/OR PROJECT MANAGER |
| | |
| | 4. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN |
| | ON THE PLAN (PERKINS EASTMAN, FS95000000559, |
| | PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS |
| | (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763, |
| | NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE |
| | NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT |
| | POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING |
| | RESPONSIBILITY FOR THE DESIGN. |
| | |
| | SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED |
| | AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES. |
| | HTML |
| | |
| | 5. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT SHOWN |
| | ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES REMAIN |
| | SEPARATE PARCELS, HAVE THEY ALREADY BEEN COMBINED WITH |
| | A UNITY OF TITLE, OR WILL THEY BE COMBINED WITH A UNITY |
| | OF TITLE? IF THEY ARE TO REMAIN SEPARATE PARCELS, SEE |
| | FBC TABLE 602, TABLE 705.8 AND REVISE PLAN TO SHOW |
| | COMPLIANCE (DISTANCE TO PROPERTY LINE, RATED WALLS AS |
| | APPLICABLE, PROTECTED OPENINGS IF PERMITTED). |
| | |
| | IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING |
| | DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING |
| | KNOWN AS TRADITIONS II PHASE ONE. |
| | |
| | THE DISTANCE OF PROPOSED BUILDING TO THE ACTUAL |
| | PROPERTY LINE (AS PER PAPA, NOT SHOWN ON PLANS) IS |
| | UNCLEAR. |
| | |
| | IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY |
| | OF TITLE AND WISH TO DO SO, THE APPLICATION IS |
| | AVAILABLE ONLINE: |
| | |
| | HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011- |
| | 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF |
| | |
| | 6. THE ADDRESS ASSIGNED TO THIS BUILDING IS 4850 LORING |
| | DRIVE; PLEASE REVISE PLANS AS APPLICABLE. |
| | |
| | 7. FS553, AS PERMITS 14120908 AND 14120909 WERE |
| | INITIALLY FOUNDATION PERMITS, PLEASE PROVIDE NEW |
| | APPLICATIONS WITH THE NEW SCOPE OF WORK AND VALUE, |
| | SIGNED BY THE QUALIFIER AND THE OWNER. ALSO PLEASE NOTE |
| | THAT IT APPEARS THAT THE NEW BUILDING (TRADITIONS II |
| | PHASE ONE) IS LOCATED PRIMARILY ON A PARCEL WITH AN |
| | ADDRESS OF 4850 LORING DRIVE, LOCATED ON TRACT C, |
| | PARCEL ID 74-42-43-12-26-003-0000. |
| | |
| | 8. SEPARATE PERMITS (PLANS, APPLICATION, REVIEWS, AND |
| | FEES) REQUIRED FOR PARKING LOT, SIGNAGE, FENCING, POOL, |
| | TRELLIS, FBC 107. |
| | |
| | 9. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT VIA |
| | EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES |
| | 78-123, 78-126. |
| | |
| | THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| | WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| | PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| | AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| | DOCUMENT THE PERMIT FILE. |
| | |
| | 10. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND |
| | RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED |
| | TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING. |
| | SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH |
| | LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE |
| | BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH |
| | LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS |
| | BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A |
| | NOTE BE INCORPORATED INTO THE PLAN. |
| | |
| | 11. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| | TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| | FBC 1609 (SUBMITTAL, NO FEE). |
| | |
| | 12. ADVISORY ONLY, POOL DETAILS NOT REVIEWED AT THIS |
| | TIME. POOL WILL BE REVIEWED UNDER A SEPARATE PERMIT, |
| | FBC 107. |
| | |
| | 13. FOR TRACKING PURPOSES, A SEPARATE PERMIT IS |
| | REQUIRED FOR THE DETACHED GENERATOR BUILDING, FBC 107. |
| | |
| | 14. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP |
| | HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND |
| | ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF |
| | ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE |
| | PLAN REVIEW PROCESS FOR THE ADDITION. |
| | |
| | 15. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| | AND OTHER INDEPENDENT STRUCTURAL ELEMENTS REQUIRE |
| | SEPARATE PERMITS WHICH WOULD INCLUDE FEES, BUILDING |
| | PERMIT APPLICATIONS, PLANS AND REVIEWS. |
| | |
| | 16. FBC 107, AN INDEX LOCATED AT THE BEGINNING OF THE |
| | DIGITAL ROLL OF PLANS WOULD BE HELPFUL. THE PLANS ARE |
| | ORDERED IN THIS MANNER: |
| | |
| | INDEX FOR PHASE I FOR ARCH/STRUCTURAL ONLY |
| | PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE, |
| | STRUCTURAL, DEMO, SITE, ARCH |
| | INDEX FOR PHASE II FOR ARCH/STRUCTURAL ONLY |
| | PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE, |
| | STRUCTURAL, DEMO, SITE, ARCH |
| | FMEP INDEX FOR PHASE II |
| | FMEP SHEETS |
| | FMEP INDEX FOR PHASE I |
| | FMEP INDEX |
| | |
| | SINCE THERE ARE 577 PLAN PAGES FOR THIS PROJECT, PLEASE |
| | PROVIDE AN INDEX AT THE BEGINNING OF THE DIGITAL ROLL. |
| | ALTHOUGH A COMPLETE SHEET INDEX IS NOT REQUIRED, AN |
| | INDEX WHICH SHOWS THE SERIES ORDER WOULD BE HELPFUL, |
| | ESPECIALLY AS PHASE II FMEP PAGES ARE LOCATED BEFORE |
| | PHASE I FMEP. |
| | |
| | 17. FBC 107, SHEET WHICH IS LABELED 201 - A626.PDF IS |
| | IN THE MIDDLE OF THE CIVIL SHEETS FOR PHASE II. PLEASE |
| | COORDINATE TO HAVE THIS PAGE RELOCATED SO IT IS IN |
| | NUMERICAL ORDER, ARCHITECTURAL SHEETS. |
| | |
| | THIS ALSO APPLIES TO SHEETS: |
| | 202 ? A630 (BETWEEN L AND S SHEETS, PHASE II) |
| | 204 - A642 |
| | 206 - A644 |
| | 209 - IN101C |
| | 210 - IN101D |
| | 2-110 ? G000B |
| | |
| | THIS MAY NOT BE A COMPLETE LIST. CHECK ALL PRIOR TO |
| | RESUBMITTAL. DUE TO NAMING CONVENTION, THE SERIES OF |
| | SHEETS DO NOT APPEAR IN THE ORDER ON THE DRAWING |
| | SCHEDULE, AND FMEP ARE NOT INCLUDED (HAVE THEIR OWN |
| | INDEXES). DUE TO THE SIZE OF THIS PLAN, WHILE NOT |
| | REQUIRED TO BE IN ORDER OF THE INDEX (ALTHOUGH THAT |
| | WOULD BE HELPFUL), THE SERIES SHOULD BE TOGETHER AND IN |
| | THE ORDER ON THE INDEX FOR THAT SERIES. |
| | |
| | 18. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS |
| | REQUIRED. |
| | |
| | 19. G001, IT APPEARS THAT THE PROPOSED BUILDING WILL BE |
| | USED AS EITHER ASSISTED LIVING OR INDEPENDENT LIVING |
| | WHICH ARE REGULATED BY FAIR HOUSING ACT, FBC 2010 |
| | ACCESSIBILITY. SHEET G001 HAS A LINE WHICH STATES THAT |
| | PER 11 9.1.4, NINE UNITS ARE REQUIRED TO BE ACCESSIBLE. |
| | PLEASE REVISE THIS INFORMATION TO CLARIFY. IF THIS IS |
| | EITHER ASSISTED LIVING OR INDEPENDENT LIVING, |
| | ACCESSIBILITY DOES NOT APPLY TO THE RESIDENTIAL PORTION |
| | OF THE BUILDING, BUT APPLIES TO PORTIONS OF THE AMENITY |
| | AND BUSINESS AREAS. ALSO, THIS REFERENCE APPEARS TO BE |
| | FROM FBC 2007; THIS SPECIFIC SECTION IS FOR TRANSIENT |
| | LODGING. PER FAIR HOUSING, ALL UNITS ARE TO CONSIDERED |
| | COVERED UNITS AND ARE TO COMPLY WITH THE REQUIREMENTS |
| | IN SECTION 3, 100.205 C. |
| | |
| | IF THE UNITS ARE NOT EITHER INDEPENDENT OR ASSISTED |
| | LIVING UNITS, PLEASE REVISE PLAN TO CLARIFY. |
| | |
| | 20. UNIT PLANS HAVE NOT BEEN REVIEWED AS ALL |
| | INFORMATION PROVIDED INDICATES THAT THEY ARE SUBJECT TO |
| | FAIR HOUSING, BUT NO INFORMATION REGARDING WAS PROVIDED |
| | ON THE UNIT PLANS, AND ACCESSIBLE UNITS ARE SHOWN. A |
| | REVIEW CANNOT BE DONE WITHOUT MORE INFORMATION, FBC |
| | 107. |
| | |
| | 21. PHASE II SHEET A101, CLARIFY USE OF GUEST ROOM 105 |
| | (REVISE PLAN TO INCLUDE INTENDED USE). IF THIS IS A |
| | ROOM AVAILABLE FOR RENT, IT APPEARS THAT THIS UNIT |
| | WOULD BE SUBJECT TO ALL REQUIREMENTS OF FBC 2010 |
| | ACCESSIBILITY. ALSO, ONE PUBLIC ACCOMODATION ROOM MAY |
| | CAUSE OTHER AREAS (SUCH AS THE POOL) TO BE SUBJECT TO |
| | ACCESSIBILITY (IN PARTICULAR, SEE FBC 2010 |
| | ACCESSIBILITY 1004, 1009). |
| | |
| | 22. G001, REQUIREMENTS ARE STATED BUT SOME THINGS ARE |
| | NOT CLEAR AS TO JOB SPECIFIC APPLICABLILITY. WILL THIS |
| | BUILDING BE CONSIDERED AN ADDITION TO THE EXISTING |
| | RESIDENTIAL TOWER (TRADITION 1), OR IS IT DESIGNED AS A |
| | SEPARATE BUILDING? SHOW COMPLIANCE WITH FBC 2010 TABLE |
| | 503. NO INFORMATION PROVIDED REGARDING THE EXISTING |
| | BUILDING. |
| | |
| | EITHER THIS IS ONE LARGE BUILDING (PROVIDE INFORMATION |
| | REGARDING THE EXISTING BUILDING) OR TWO SEPARATE |
| | BUILDINGS WITH AN ASSUMED PROPERTY LINE (SHOW |
| | COMPLIANCE FBC 705.3. REVISE PLAN TO CLARIFY. |
| | |
| | 23. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE |
| | BUILDINGS, A 2 HOUR FIRE WALL IS SHOWN, 3 HOURS |
| | REQUIRED PER FBC TABLE 706.4. |
| | |
| | 24. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE |
| | BUILDINGS, THE FIRE WALL IS TO COMPLY WITH THE |
| | REQUIREMENT OF 706.2, STRUCTURAL INTEGRITY. |
| | |
| | 25. G101, CLARIFY THE EXIT STRATEGY FOR THE CONNECTING |
| | DOOR BETWEEN TRADITION I AND II. IF THIS IS AN EXIT FOR |
| | BOTH SIDES, HOW WILL THE DOOR SWING IN BOTH DIRECTIONS, |
| | AND HOW WOULD YOU CONTROL CONFLICTS SUCH AS OCCUPANTS |
| | TRAVELING IN OPPOSITE DIRECTIONS? IT IS NOT CLEAR HOW |
| | THE FIRE WALL WILL ALLOW OCCUPANTS TO PASS THROUGH. IF |
| | THIS IS TO BE A MCKEON DOOR, IT IS NOT CLEAR HOW THIS |
| | WILL MEET THE STRUCTURAL INTEGRITY REQUIREMENT. |
| | |
| | REVISE PLAN TO INCLUDE A DETAIL FOR THE PROPOSED FIRE |
| | WALL AND CLARIFY THE ABOVE CONCERNS, FBC 107. |
| | |
| | 26. G101, CORRIDOR 187 IS NOT A RATED CORRIDOR BUT |
| | SERVES THE RESIDENTIAL UNITS AS THERE IS AN EXIT SIGN |
| | FROM CORRIDOR 188 TO CORRIDOR 187, FBC TABLE 1018.1. |
| | THERE IS A NOTE WHICH STATES THAT TRAVEL DISTANCE IS |
| | 134FT, BUT IT IS NOT CLEAR WHERE THIS IS APPLICABLE. |
| | |
| | 27. A101, FBC 1022.4, STAIR 1, OPENINGS INTO THE STAIR |
| | ARE LIMITED TO THOSE REQUIRED FOR EXITING. THE |
| | RATIONALE FOR HAVING AN EXIT FOR THE CHILLERS GO |
| | THROUGH THE EXIT FOR THE RESIDENTIAL IS NOT CLEAR; IF |
| | TWO EXITS ARE REQUIRED FROM THIS SPACE, IT APPEARS THAT |
| | THERE IS ENOUGH ROOM TO ADD A DOOR IN ANOTHER LOCATION. |
| | |
| | 28. SOME MECHANICAL SHEETS DO NOT SHOW THE REQUIRED |
| | FIRE RATING (FBC708) FOR THE ADJACENT SHAFT FOR THE |
| | PRESSURIZED STAIRS (FOR INSTANCE, 305 M202A), PLEASE |
| | CORRELATE. |
| | |
| | 29. G001 MAKES REFERENCE TO THE EXCEPTION FOR A 1 HOUR |
| | SHAFT RATING PER FBC 403.2.1.2. INCORPORATE THIS |
| | REQUIREMENT INTO THE FIRE PROTECTION SHEETS. A BUILDING |
| | REVIEW WILL BE DONE IN ADDITION TO FIRE AND MECHANICAL |
| | REVIEWS WHEN THE FIRE SPRINKLER PERMIT APPLICATION AND |
| | PLANS ARE SUBMITTED. NOTE THAT FLOOR PLANS SHOW A 2 |
| | HOUR SHAFT RATING. CLARIFY WHERE THIS EXCEPTION WILL |
| | APPLY. IF THIS EXCEPTION DOES NOT APPLY, REMOVE FROM |
| | PLAN AND ADVISE. |
| | |
| | 30. G101 AND OTHER PAGES, REVISE LIFE SAFETY PLAN TO |
| | SHOW EXIT DISCHARGE TO THE PUBLIC WAY FOR ALL EXITS. |
| | |
| | EXIT DISCHARGE NOT CLEAR FOR THE EXITS WHICH OPEN TO |
| | THE POOL AREA AND FOR THE EXITING FROM CORRIDOR THROUGH |
| | THE DINING ROOM EXTENSION, FBC 1027. EXIT STRATEGY IS |
| | NOT CLEAR. SEE FIRE COMMENTS. SEE ALSO 1004.8 (OUTDOOR |
| | AREAS), 1006.1.1 (ILLUMINATION). TWO REQUIRED EXITS |
| | FROM DINING ROOM OPEN INTO THE POOL AREA. THE POOL AREA |
| | ITSELF HAS A HIGH OCCUPANT LOAD. IT IS NOT CLEAR HOW |
| | HUNDREDS OF OCCUPANTS WILL TRAVEL FROM THE POOL AREA TO |
| | THE PUBLIC WAY; ONLY A SMALL GATE IS SHOWN AND THE |
| | OCCUPANTS WILL HAVE TO CROSS AN AREA MARKED FOR THE |
| | FIRE TRUCK. |
| | |
| | OTHER EXITS SHOW SIDEWALKS BUT ACCESS TO THE PUBLIC WAY |
| | (OR OTHER APPROVED AREA) IS NOT CLEAR. FOR INSTANCE, |
| | FP001 SHOWS A SIDEWALK FOR EXIT STAIRS 3 AND 4 WHICH |
| | LEADS BACK INTO THE BUILDING. |
| | |
| | 31. G101, STAIR 4, FBC 1022.6, IN ORDER TO FACILITATE |
| | PHASE II, THE EXTERIOR WALL IS TO BE FIRE RESISTANCE |
| | RATED (LESS THAN 180DEGREES WHEN PHASE II IS BUILT). |
| | |
| | 32. G101, THEATER VESTIBULE AND MULTIPURPOSE ROOM (ALSO |
| | REFERRED TO AS THEATER ON SHEET G001, USE GROUP |
| | CLASSIFICATION) IS SHOWN AS GROUP A1. SHEET G001 ALSO |
| | REFERS TO MULTIPURPOSE AS A3. |
| | |
| | 33. A101, SHOW 18IN MANEUVERING CLEARANCE PULL SIDE, |
| | FOR THE FOLLOWING DOORS PER FBC 2010 ACCESSIBILITY |
| | 404.2.4: |
| | |
| | AEROBICS ROOM 146 |
| | ACCESSIBLE CHANGING ROOM 149 |
| | |
| | 34. A101A, WHEN RESUBMITTING, INCLUDE SEATING PLAN FOR |
| | THE MULTIPURPOSE ROOM. |
| | |
| | NOTE: SEATING REVIEWED IN PLANGRID, A101A. FORTY SEVEN |
| | FIXED SEATS SHOWN, OCCUPANT LOAD IS 51. |
| | |
| | REVISE PLAN TO INCLUDE INFORMATION REGARDING THE USE OF |
| | THIS SPACE. WILL THIS BE ONLY FOR RESIDENTS AND THEIR |
| | GUESTS (FAIR HOUSING), OR WILL TICKETS EVER BE SOLD TO |
| | THE GENERAL PUBLIC (ACCESSIBILITY)? |
| | |
| | NO ACCESSIBLE SEATING IS SHOWN. SEE FBC 2010 |
| | ACCESSIBILITY 802 REGARDING WHEELCHAIR SPACES, SIGHT |
| | LINES, AND COMPANION SPACES REQUIRED. REVISE PLAN TO |
| | CLARIFY COMPLIANCE FOR ACCESSIBILITY OR FAIR HOUSING |
| | (REQUIREMENT THAT ALL PUBLIC AND COMMON USE AREAS ARE |
| | READILY ACCESSIBLE TO AND USABLE BY DISABLED PERSONS) |
| | AS APPLICABLE. |
| | |
| | 35. EXERCISE AREAS, MULTIPURPOSE ROOM (SEE OTHER |
| | COMMENT), SALON, SPA, POOL, DINING, GUEST ROOM, ALL |
| | COMMON AREAS, REVISE PLAN TO INDICATE WHETHER THESE |
| | AREAS ARE FOR RESIDENTS AND THEIR GUESTS ONLY (SUBJECT |
| | TO FAIR HOUSING ONLY) OR IF THE PORTION OF THE FACILITY |
| | IS OPEN TO NON RESIDENTS FOR A FEE, OR AVAILABLE FOR |
| | EMPLOYEE USE (SUBJECT TO ACCESSIBILITY AS WELL AS FAIR |
| | HOUSING). |
| | |
| | 36. G101 AND A213, THE DOORS FOR THE MULTI PURPOSE ROOM |
| | INCLUDE SIDELIGHTS WHICH APPEAR TO BE IDENTICAL TO THE |
| | DOORS BUT DO NOT OPERATE. SEE FBC 1008.1, REVISE PLAN |
| | TO SHOW HOW THE DOORS WILL BE EASILY DISTINGUISHABLE |
| | FROM THE INOPERABLE SIDELITES. |
| | |
| | 37. G101 OR RELATED A SHEET, REVISE PLAN TO INCLUDE |
| | INFORMATION REGARDING WHAT WILL BE STORED IN THE |
| | CHEMICAL ROOM 137A (ASSOCIATED WITH SALON), FBC 107, |
| | FBC 307. PLAN SHOULD INCLUDE A BRIEF DESCRIPTION OF |
| | CHEMICALS TO BE STORED AND, IF ANY CHEMICALS ARE THOSE |
| | LISTED IN FBC307, INCLUDE CHEMICAL AND AMOUNT TO SHOW |
| | THAT IT IS BELOW THE ALLOWABLE LIMIT. |
| | |
| | 38. G101, AEROBICS 146 AND FITNESS 143 APPEAR TO HAVE |
| | AN OCCUPANT LOAD OVER 50, BUT SECOND EXIT ACCESS NOT |
| | CLEAR. AEROBICS ROOM HAS TWO DOORS BUT BOTH LEAD TO |
| | SAME CORRIDOR (COMMON PATH). FITNESS ROOM HAS ONLY ONE |
| | EXIT ACCESS. TWO MEANS OF EGRESS REQUIRED FROM SPACES |
| | WITH AN OCCUPANT LOAD OVER 50, TWO EXITS REQUIRED FOR |
| | THE AREA. |
| | |
| | 39. G101, CORRIDOR 146A APPEARS TO EXCEED DEAD END |
| | CORRIDOR LIMIT, FBC 1018.4. REVISE PLAN TO ADDRESS. |
| | |
| | 40. G101, FBC 303, FITNESS LOUNGE, FITNESS, AEROBICS, |
| | BREAK ROOM, CONFERENCE ROOM, LIBRARY ARE ASSEMBLY |
| | OCCUPANCY, FBC 303. PROVIDE OCCUPANT LOAD (TABLE |
| | 1004.1.1, EXERCISE ROOMS) AND SEPARATION BETWEEN |
| | ASSEMBLY AND BUSINESS UNLESS EXCEPTION APPLIES. IF |
| | COVERED UNDER AN EXCEPTION, INCORPORATE INTO PLAN (FBC |
| | 508.1, 508.2 AND COMMENTARY). |
| | |
| | 41. LIVING ROOM LIBRARY IS SHOWN AS A CIRCULATION AREA |
| | WITH OCCUPANT LOAD BASED ON 200 SF PER PERSON. FBC |
| | TABLE 1004, READING ROOMS ARE TO HAVE AN OCCUPANT LOAD |
| | OF 50 SF PER PERSON. REVISE PLAN TO CLARIFY THE USE AND |
| | OCCUPANT LOAD FOR THIS AREA. |
| | |
| | 42. G101, REVISE PLAN TO INCLUDE OCCUPANT LOAD AND AREA |
| | FOR THE FITNESS ROOM AND AEROBICS ROOM (SEPARATELY AS |
| | THE LARGER AREA CAN BE COMBINED TO TWO SMALLER AREAS). |
| | AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA |
| | OCCUPANT LOAD WILL BE OVER 50, DOORS ARE TO SWING IN |
| | THE DIRECTION OF TRAVEL, FBC 1008.1.2. |
| | |
| | 43. AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA |
| | OCCUPANT LOAD WILL BE OVER 50, FIRE EXIT HARDWARE OR |
| | PANIC HARDWARE REQUIRED FOR THOSE DOORS AND ALL OTHER |
| | DOORS IN THE MEANS OF EGRESS, FBC 1008.1.10, 1004.9. |
| | |
| | 44. EGRESS GATE IS REQUIRED TO HAVE EITHER FIRE EXIT |
| | HARDWARE OR PANIC HARDWARE, FBC 1008.1.10, 1008.2. |
| | REVISE PLAN TO INCLUDE THE REQUIREMENT OR DETAIL. |
| | |
| | 45. G101, FBC 911.1.1, FIRE COMMAND CENTER ROOM SHALL |
| | BE A MINIMUM OF 200 SF AND A MINIMUM DIMENSION OF 10FT; |
| | REVISE PLAN TO SHOW COMPLIANCE WITH SIZE REQUIREMENT. |
| | |
| | 46. G101, FBC 911.1.2, FIRE COMMAND CENTER ROOM |
| | REQUIRES A 1 HOUR FIRE BARRIER; THIS IS SHOWN AT THE |
| | CORRIDOR BUT NOT BETWEEN FIRE COMMAND CENTER AND |
| | CHILLERS RM 182. |
| | |
| | 47. G101, PROVIDE OCCUPANT LOAD FOR DINING F. IF THE |
| | OCCUPANT LOAD IS OVER 50, TWO EXITS REQUIRED. REQUIRED |
| | MEANS OF EGRESS DOORS ARE TO BE SIDE SWINGING; A |
| | SLIDING DOOR IS SHOWN AS SECOND MEANS OF EGRESS, FBC |
| | 1008.1.2. |
| | |
| | 48. FBC 911.1.4, LAYOUT OF FIRE COMMAND CENTER AND ALL |
| | FEATURES REQUIRED BY 911.1.5 TO BE SUBMITTED AND |
| | APPROVED PRIOR TO INSTALLATION. |
| | |
| | 49. TK G102, RATING BETWEEN STAIR 2, STAIR 4 IS SHOWN |
| | BETWEEN ADJACENT SHAFTS FOR PRESSURIZATION ON SHEET |
| | M202A, G102 SHOWS THE RATING OUTSIDE THE SHAFT (BETWEEN |
| | SHAFT AND CORRIDOR). |
| | |
| | 50. G102 AND OTHER FLOORS, PROVIDE OCCUPANT LOAD AND |
| | OCCUPANCY CLASSIFICATION FOR THE COMMUNITY ROOM AND |
| | CONCIERGE 936, FBC 107, SEE ALSO FBC 508.2. |
| | |
| | NOTE THAT IF OCCUPANT LOAD IS 50 OR MORE, TWO EXITS ARE |
| | REQUIRED. |
| | |
| | 51. A610, REVISE DOOR NOTE (GENERAL GLAZING |
| | REQUIREMENTS) TO UPDATE CODE REFERENCE (FBC 2007). |
| | |
| | 52. DOOR SCHEDULE HAS A COLUMN FOR ?ELECTRIC? BUT THAT |
| | COLUMN IS BLANK. IT APPEARS THAT THIS SHOULD BE |
| | APPLICABLE FOR SLIDING DOORS IN THE REQUIRED MEANS OF |
| | EGRESS AND EXIT. EXIT DOOR 122 (DOOR TYPE G1) SHOULD |
| | ALSO COMPLY WITH FBC 1008.1.4.2, 1008.1.4.3. |
| | |
| | 53. A601 AND G101, DOORS IN FIRE BARRIERS REQUIRE A 45 |
| | MINUTE FIRE RATING, FBC TABLE 715.4. IT IS NOT CLEAR |
| | WHICH DOORS ARE BEING CONSIDERED IN A CORRIDOR RATHER |
| | THAN AN OCCUPANCY SEPARATION. SEE DOORS 173C, 182, 172, |
| | 183. |
| | |
| | DOOR 173C IS A 20 MINUTE DOOR, BUT THE CORRIDOR 184 |
| | RATING IS NOT CONTINUOUS AS IT APPEARS TO TRANSITION |
| | INTO THE GALLERY. USE OF CORRIDORS, INCIDENTAL AND |
| | ACCESSORY USES FBC 508 ARE NOT ENTIRELY CLEAR. IF ANY 1 |
| | HOUR RATINGS ON THE PLAN ARE REMOVED WHEN RESUBMITTING, |
| | PLEASE ALSO NOTE ALSO SMOKE AND PROTECTION REQUIREMENT |
| | IN 508.2.5.2. |
| | |
| | 54. S8.1 AND G000 PHASE I AND II, MAP FOR IMPORTANCE |
| | FACTOR III & IV IS INCLUDED, BUT SHEET S8.1 STATES |
| | DESIGN CRITERIA AS RISK CATEGORY II; PLEASE CORRELATE. |
| | |
| | IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL |
| | BUILDING OCCUPANT LOAD. AT THIS POINT IT IS NOT CLEAR |
| | WHETHER THE TOTAL OCCUPANT LOAD SHOULD INCLUDE |
| | TRADITION I AND TRADITION II, OR IF THE TWO WILL BE |
| | DESIGNED AS SEPARATE BUILDINGS. |
| | |
| | 55. S8.1, SOME STANDARD REFERENCES REFER TO "LATEST |
| | EDITION." PLEASE REVISE TO BE THE VERSION SPECIFIED IN |
| | FBC CHAPTER 35. |
| | |
| | 56. S9.1, SECTION 9 AND OTHER PLACES, PLYWOOD |
| | SPECIFIED. FBC 603.1, PLEASE REVISE TO FRT. |
| | |
| | 57. AN ENCLOSED ELEVATOR LOBBY IS NOT SHOWN. FBC |
| | 708.14.1, PLEASE ADVISE AS TO WHICH EXCEPTION IS BEING |
| | USED IN THIS DESIGN AND WHERE THIS INFORMATION CAN BE |
| | LOCATED ON THE PLAN. |
| | |
| | 58. A002 AND OTHER SHEETS REFER TO UL ASSEMBLIES. |
| | INCORPORATE DETAILS WITH SPECIFIC OPTIONS INTO THE PLAN |
| | OR THIS PERMIT WILL BE ISSUED WITH PROVISO THAT THE |
| | DETAILS BE SUBMITTED PRIOR TO INSTALLATION, AFTER |
| | REVIEW BY DESIGNER OF RECORD. |
| | |
| | 59. A101, A "W" SHAPE APPEARS IN FRONT OF DOORS AT 186 |
| | ELEVATOR LOBBY AND 118 WOMEN WHICH DOES NOT APPEAR ON |
| | OTHER SHEETS, CLARIFY, FBC 107. |
| | |
| | 60. FBC 1207, PROVIDE THE FOLLOWING TEST REPORTS FOR |
| | THE FLOORING UNDERLAYMENT WILL BE REQUIRED AS |
| | APPLICABLE (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR |
| | SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR |
| | LESS ARE ACCEPTABLE): |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM |
| | E 84 OR UL 723. |
| | |
| | IF THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT |
| | ISSUANCE, PERMIT WILL BE ISSUED WITH PROVISO THAT THIS |
| | BE SUBMITTED PRIOR TO INSTALLATION. REVIEW BY DESIGNER |
| | OF RECORD REQUIRED PRIOR TO SUBMITTAL, FBC 107.3.4.1. |
| | |
| | 61. PROVIDE THE GEOTECHNICAL REPORT FOR THIS PROJECT, |
| | FBC 1803. THE SOILS REPORT IS TO BE REVIEWED BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | |
| | 62. FBC 107, PROVIDE THE SURVEY FOR THIS PROPERTY. |
| | |
| | 63. THE PLANS INDICATE THERE WILL BE A POOL BUILT VERY |
| | CLOSE TO THIS BUILDING PLEASE PROVIDE HOW THE |
| | FOUNDATION /FOOTING WILL BE PRESERVED WHILE THE POOL IS |
| | BEING EXCAVATED? 1808.7. |
| | |
| | 64. 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE |
| | PROTECTION SHALL BE PROVIDED BY REGISTERED |
| | TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES, |
| | BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR |
| | OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED |
| | FOR USE AS A PREVENTATIVE TREATMENT TO NEW |
| | CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF THE TERMITE |
| | PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL |
| | BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED |
| | PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING |
| | STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES. |
| | TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES." |
| | |
| | 65. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 66. PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL |
| | COMPLY WITH : |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF |
| | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| | PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| | COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| | ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| | NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| | POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| | EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| | OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| | DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO |
| | THE PLAN. |
| | |
| | 67. G101, REVISE LIFE SAFETY PLAN TO INCLUDE WORST CASE |
| | WITH TRAVEL DISTANCE FOR EACH AREA (NOT NECESSARY FOR |
| | EACH ROOM). PATH OF TRAVEL IS TO BE SHOWN ACROSS THE |
| | DIAGONAL OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN |
| | ALONG THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS |
| | FURNITURE WILL BE PLACED IN THE CENTER OF THE ROOM, THE |
| | PATH SHOULD BE MEASURED ALONG THE ROOM PERIMETER. |
| | |
| | 68. SEE OTHER COMMENTS, SHAFT RATING PROPOSED NOT |
| | CLEAR. PLEASE CLARIFY SHAFT RATING FOR ELEVATOR 2 PHASE |
| | I, A 1 HOUR SHAFT IS SHOWN, BUT A 2 HOUR SHAFT IS SHOWN |
| | FOR ELEVATOR 1 |
| | |
| | 69. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE |
| | (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY |
| | AS APPLICABLE. PLEASE ALSO REVISE OTHER AFFECTED |
| | SHEETS. |
| | |
| | 70. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES, |
| | PLYWOOD SHEATHING SHOWN. FBC 602.1, REVISE TO INCLUDE |
| | REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND |
| | OTHER SHEETS), FBC 603.1.1.1.3. |
| | |
| | 71. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC |
| | SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS. |
| | ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR |
| | ACCESS FOR MAINTENANCE, FBC 107. |
| | |
| | 72. 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY |
| | WITH THIS SECTION. |
| | |
| | 73. PLANS IN MANY LOCATIONS USE THE LANGUAGE "UNDER |
| | SEPARATE PERMIT" (FOR INSTANCE, SHEET 036 - S6.2). IF |
| | ALL WORK TO BE INCLUDED IN THIS PERMIT, REVISE |
| | LANGUAGE. IF THIS IS PROVIDED FOR INFORMATION ONLY, |
| | PLEASE ADVISE. |
| | |
| | 74. INCORPORATE FIRE RATING REQUIREMENTS AND DETAILS |
| | FOR THE FLOOR, STRUCTURAL ELEMENTS FBC TABLE 601. |
| | |
| | 75. PLEASE IDENTIFY THE RECTANGLE ADJACENT TO THE SINK |
| | IN THE GUEST ROOM, S1.2 AND OTHER PAGES. |
| | |
| | 76. PROVIDE A DETAIL FOR THE OVERFLOW SCUPPER, FBC 107 |
| | (OR ADVISE AS TO WHERE THIS CAN BE LOCATED). |
| | |
| | |
| | |
| | |
| | |
| | |
| | |