| Date |
Text |
| 2015-03-13 13:52:38 | 4920 LORING DRIVE |
| | PERMIT #14120909 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY |
| | REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE |
| | (2012 EDITION WITH FLORIDA AMENDMENTS.) |
| | |
| | GENERAL: INDICATE THE LOCATION AND SIZES OF ANY |
| | PROPOSED CONSTRUCTION TRAILERS/MODULAR BUILDINGS. PER |
| | NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| | ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| | TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| | COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| | CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| | TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| | PER TABLE 4.2.1: |
| | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| | 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| | ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| | 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| | SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| | **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| | BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| | SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| | PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| | TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| | PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| | PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE |
| | EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER |
| | OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| | MIXED OCCUPANCY. |
| | |
| | SHEET G101: FIRE COMMAND CENTER (#182B) SHALL BE AT |
| | LEAST 200 SQUARE FEET AND HAVE A MINIMUM DIMENSION OF |
| | 10 FEET (FBC 911.1.3). PER NFPA 1 SECTION 11.9.2 THE |
| | EMERGENCY COMMAND CENTER SHALL BE SEPARATED FROM THE |
| | REMAINDER OF THE BUILDING BY A FIRE BARRIER HAVING A |
| | FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR. |
| | PER NFPA 1 SECTION 11.9.4 THE FOLLOWING SHALL BE |
| | PROVIDED IN THE EMERGENCY COMMAND CENTER: |
| | (1) THE FIRE DEPARTMENT COMMUNICATION UNIT |
| | (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| | ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| | (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| | FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF |
| | EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| | EQUIPMENT, AND FIRE DEPARTMENT ACCESS |
| | (4) WORK TABLE |
| | (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS |
| | FOR THE BUILDING |
| | |
| | PER NFPA 1 SECTION 11.9.5 WHERE OTHERWISE REQUIRED, THE |
| | FOLLOWING DEVICES OR FUNCTIONS SHALL BE PROVIDED WITHIN |
| | THE EMERGENCY COMMAND CENTER: |
| | (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT |
| | (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT |
| | (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE |
| | ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| | (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| | SYSTEMS |
| | (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| | SIMULTANEOUSLY |
| | (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| | PANELS |
| | (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| | (8) FIRE PUMP STATUS INDICATORS |
| | (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| | TRANSFER FEATURES |
| | (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| | BY OTHER SECTIONS OF THIS CODE |
| | (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| | |
| | 11.9.6 EMERGENCY COMMAND CENTER ACCEPTANCE TESTING. |
| | DEVICES, EQUIPMENT, COMPONENTS, AND SEQUENCES SHALL BE |
| | INDIVIDUALLY TESTED IN ACCORDANCE WITH APPROPRIATE |
| | STANDARDS AND MANUFACTURERS? DOCUMENTED INSTRUCTIONS. |
| | |
| | SHEET G101: PER TABLE 7.3.1.2, KITCHEN SPACES SHALL |
| | HAVE AN OCCUPANT LOAD FACTOR OF 100 SQUARE FEET PER |
| | PERSON IN LIEU OF THE 200 SQ.FT. INDICATED. |
| | |
| | SHEET G101: PROVIDE AN OCCUPANT LOAD FOR BREAKROOM |
| | #167. |
| | |
| | SHEET G101: LIBRARY #121, FITNESS #143, AEROBICS #145 |
| | AND CONFERENCE #112 ARE TREATED AS ASSEMBLY USE SPACES |
| | IN THE FIRE CODE AND NEED AN OCCUPANT LOAD BASED UPON |
| | THE OCCUPANT LOAD FACTORS FOUND IN TABLE 7.3.1.2. |
| | |
| | ***SHEET G101: SEVERAL EXITS APPEAR TO ROUTE AND MERGE |
| | EXITING OCCUPANTS AT THE POOL DECK AREA. THERE DOES NOT |
| | APPEAR EXTERIOR EXIT SIGNAGE, EMERGENCY LIGHTING OR |
| | SUFFICIENT EXIT WIDTH (1 EGRESS GATE) TO HANDLE THE |
| | OCCUPANT LOAD. WHERE IS THE PUBLIC WAY? HOW WILL THE |
| | POOL DECK EGRESS ROUTES BE MAINTAINED UNOBSTRUCTED FOR |
| | THE LIFE OF THE BUILDING? |
| | |
| | SHEET G101: CORRIDOR #146A CREATES A DEAD-END THAT |
| | EXCEEDS 20 FEET. PER SECTION12.2.5.1.3 DEAD-END |
| | CORRIDORS SHALL NOT EXCEED 20 FEET. |
| | |
| | SHEET C103 &C106: SOUTH ACCESS ROAD INDICATES A 20 FOOT |
| | WIDE FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST |
| | AREA INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE |
| | 20 FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION |
| | 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS |
| | SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE |
| | APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL |
| | HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND |
| | AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| | FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE |
| | LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING, |
| | "FIRE LANE - NO PARKING BY ORDER OF THE FIRE |
| | DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE |
| | BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF |
| | SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS |
| | SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED |
| | A MAXIMUM OF 60 FEET APART. |
| | |
| | SHEET C107: FIRE HYDRANTS SHALL BE INSTALLED, |
| | INSPECTED, TESTED AND APPROVED BY THE FIRE DEPARTMENT |
| | PRIOR TO VERTICAL CONSTRUCTION.PER SECTION 18.3.4.1 |
| | (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH |
| | CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO |
| | THE BACKSIDE OF THE STEAMER CAP. |
| | |
| | SHEET C107: NORTHWEST PIV - PER NFPA 24 SECTION 6.2.1, |
| | ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE |
| | PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH |
| | ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED: |
| | (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40 |
| | FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST |
| | INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED |
| | CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE |
| | BUILDING AS THE HEIGHT OF THE WALL FACING THE POST |
| | INDICATOR VALVE. |
| | (2) A WALL POST INDICATOR VALVE |
| | (3) AN INDICATING VALVE IN A PIT, INSTALLED IN |
| | ACCORDANCE WITH SECTION 6.4 |
| | (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING |
| | VALVE NOT LESS THAN 40 FEET FROM THE BUILDING. |
| | (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A |
| | BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE |
| | SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET |
| | BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF |
| | THE WALL FACING THE BACKFLOW PREVENTER. |
| | (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM |
| | ACCESSIBLE FROM THE EXTERIOR |
| | (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE |
| | ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE |
| | AUTHORITY HAVING JURISDICTION |
| | |
| | SHEET C107: PER FBC SECTION403.3.2 WATER SUPPLY TO |
| | REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE |
| | SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS |
| | LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING |
| | SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER |
| | MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY |
| | PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE |
| | SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE |
| | PUMPS TO OPERATE. |
| | |
| | SHEET A101: CHILLER #182 HAS A DOOR LEADING INTO THE |
| | FIRE RATED STAIR ENCLOSURE. PER SECTION 7.1.3.2.1 DOORS |
| | INTO EXIT ENCLOSURES ARE ONLY PERMITTED FOR NORMALLY |
| | OCCUPIED ROOMS. |
| | |
| | SHEET A101C: THE COOKING GRILL LOCATED ON THE POOL DECK |
| | SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST |
| | 10 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES |
| | PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED |
| | UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH |
| | NFPA 96. |
| | |
| | SHEET A101D: PLANS SHOW OCCUPANTS USING CORRIDOR #185 |
| | AS A MEANS OF EXIT ACCESS; HOWEVER, BOTH SIDES OF THE |
| | DOOR APPEAR TO BE ACCOMODATING MORE THAN 50 PERSONS AND |
| | WOULD NEED TO SWING IN BOTH DIRECTIONS OF EGRESS. |
| | |
| | SHEET A102B: TRASH ROOM #205C WALL ADJACENT TO |
| | RESIDENTIAL ROOM DOES NOT APPEAR TO BE FIRE RATED. |
| | TYPICAL ALL LEVELS. |
| | |
| | SHEET A490: PER SECTION 7.2.2.5.4 - STAIRWAY |
| | IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR |
| | MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE |
| | OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L). |
| | (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE |
| | WITHIN THE ENCLOSURE AT EACH FLOOR LANDING. |
| | (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL. |
| | (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP |
| | AND BOTTOM OF THE STAIR ENCLOSURE. |
| | (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF |
| | THE STAIR ENCLOSURE. |
| | (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND |
| | THE DIRECTION TO, EXIT DISCHARGE. |
| | (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE |
| | APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A |
| | POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN |
| | OR CLOSED POSITION. |
| | (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE. |
| | (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE |
| | WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE |
| | WALL. |
| | (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED |
| | AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH |
| | LETTERING. |
| | (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED |
| | UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL |
| | DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS. |
| | LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH. |
| | (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE |
| | MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS. |
| | MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER |
| | APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR |
| | NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B" |
| | OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING |
| | THE FLOOR LEVEL NUMBER. |
| | (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF |
| | THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN |
| | IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS. |
| | |
| | SHEET FP001: ALL NFPA STANDARDS REFERENCES SHALL BE |
| | UPDATED TO REFLECT THOSE ADOPTED IN THE 5TH EDITION OF |
| | FLORIDA FIRE PREVENTION CODE EFFECTIVE DECEMBER 31, |
| | 2014. FOR EXAMPLE. THE SPRINKLER AND STANDPIPE DESIGNS |
| | SHALL CONFORM TO THE 2010 EDITION OF NFPA 13 AND NFPA |
| | 14 RESPECTIVELY. |
| | |
| | STANDPIPE DESIGN: PROVIDE 2-1/2" OUTLETS ONLY. REMOVE |
| | THE 1-1/2" REDUCING COUPLINGS ON ALL FIRE DEPARTMENT |
| | VALVES. |
| | |
| | SHEET FP201B: TRASH ROOM #105C IS MISSING THE |
| | DESIGNATION FOR ORDINARY HAZARD SPRINKLER PROTECTION. |
| | TYPICAL ALL FLOORS. |
| | |
| | SHEET FP402: ENGINEERING DOCUMENTS ARE REQUIRED TO |
| | INDICATE THE WATER SUPPLY RESULTS FROM A CURRENT |
| | HYDRANT FLOW TEST. FIRE PUMP SCHEDULE DOES NOT INDICATE |
| | A RATED PRESSURE OR HORSEPOWER RATING. THE ENGINEERING |
| | DOCUMENTS WILL BE REQUIRED TO DETERMINE IF PRESSURE |
| | REDUCING VALVES ARE NEEDED ON THE STANDPIPES AND |
| | SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL ALSO |
| | REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH DRAIN |
| | RISER AS SHOWN ON THE PLANS. |
| | |
| | SHEET FP402: PER FBC SECTION403.3.2 WATER SUPPLY TO |
| | REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE |
| | SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS |
| | LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING |
| | SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER |
| | MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY |
| | PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE |
| | SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE |
| | PUMPS TO OPERATE. |
| | |
| | |
| | SHEET M201B: ALL HVAC KEY NOTES APPEAR TO BE MISLABLED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | PHASE 2 - FIRE DEPARTMENT REVIEW |
| | |
| | SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH |
| | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH |
| | CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101 |
| | WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE |
| | EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER |
| | OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A |
| | MIXED OCCUPANCY. |
| | |
| | SHEET G101: THE FIRE RATING FOR STAIR #4 DOES NOT |
| | CONTINUE TO THE EXTERIOR WALLS OR DOORS. PER SECTION |
| | 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED |
| | OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY AND THE |
| | WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE |
| | BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES, THE |
| | BUILDING ENCLOSURE WALLS WITHIN 10 FEET HORIZONTALLY OF |
| | THE NONRATED WALL OR UNPROTECTED OPENING SHALL BE |
| | CONSTRUCTED AS REQUIRED FOR STAIRWAY ENCLOSURES, |
| | INCLUDING OPENING PROTECTIVES. PER SECTION 7.2.2.5.2.2 |
| | CONSTRUCTION SHALL EXTEND VERTICALLY FROM THE FINISHED |
| | GROUND LEVEL TO A POINT 10 FEET ABOVE THE TOPMOST |
| | LANDING OF THE STAIRS OR TO THE ROOFLINE, WHICHEVER IS |
| | LOWER. |
| | |
| | SHEET L101: SOUTH ACCESS ROAD INDICATES A 20 FOOT WIDE |
| | FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST AREA |
| | INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE 20 |
| | FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION |
| | 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS |
| | SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE |
| | APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL |
| | HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND |
| | AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13 |
| | FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE |
| | LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING, |
| | "FIRE LANE - NO PARKING BY ORDER OF THE FIRE |
| | DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE |
| | BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF |
| | SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS |
| | SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED |
| | A MAXIMUM OF 60 FEET APART. |
| | |
| | |
| | |
| | DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT |
| | RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE |
| | RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION |
| | 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT |
| | ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED |
| | WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL, |
| | ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE |
| | TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT |
| | THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A |
| | CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR |
| | VIOLATIONS OF THIS CODE. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |