| Date |
Text |
| 2015-06-23 15:12:32 | 6/12/2015 |
| | PROJECT: MORSE SENIOR CENTER PHASE |
| | PERMIT#: 14120909 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) CLARIFICATION IS REQUIRED. THE APPLICATION SUBMITTED |
| | WITH THESE PLANS STATE "FOUNDATION ONLY" HOWEVER THE |
| | PLANS ARE A FULL SET FOR CONSTRUCTION OF A HIGH RISE. |
| | |
| | 2) G001 |
| | UNDER APPLICABLE CODES LIST TOP LEFT OF THE PAGE ADD |
| | THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE |
| | |
| | 3) E000 |
| | UNDER CODES AND STANDARDS LIST TOP RIGHT OF THE PAGE. |
| | CHANGE THE 2011 EDITION OF THE NATIONAL ELECTRICAL CODE |
| | TO THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE. |
| | |
| | 4) E001 |
| | SUBMIT MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR |
| | AND CONTROLLER/ATS. INDICATE HP RATING LOAD AND VOLTAGE |
| | OF FIRE PUMP MOTOR. |
| | 4A) PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE |
| | PUMP FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL |
| | WIRING AND PUMP WIRING ARE APPROPRIATELY FIRE |
| | PROTECTED. INDICATE THE FIRE RATING AND MATERIAL |
| | REQUIRED. NEC 695.6, 695.14 |
| | |
| | 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING |
| | NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR, |
| | PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE |
| | ACCESSORIES. |
| | 5A) VERIFY THE MAXIMUM VOLTAGE DROP IS NOT MORE THAN 15 |
| | % BELOW NORMAL STARTING AND 5% BELOW WHEN THE MOTOR IS |
| | OPERATING AT 115% OF THE FULL LOAD CURRENT RATING. NEC |
| | 695.6, 695.7 |
| | |
| | 6) CLARIFY THE NEED FOR EMERGENCY POWER AND THEREFORE |
| | THE NEED FOR LEGALLY REQUIRED EMERGENCY GENERATOR OR |
| | SIMPLY A STANDBY STAND BY GENERATOR. |
| | |
| | 7) INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE |
| | IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY |
| | INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC |
| | 700.9 |
| | |
| | 8) PROVIDE PROPER SIGNAGE INDICATING THE TYPE AND |
| | LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC |
| | 700.8 |
| | 8A) PERMANENT PLAQUES OR DIRECTORIES SHALL BE INSTALLED |
| | AT EACH SERVICE DISCONNECT |
| | DENOTING ALL OTHER SERVICE LOCATION. NEC 230.2(E) |
| | |
| | 9) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | |
| | 10) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 12) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL |
| | POWER AND LIGHTING SYSTEMS. (MANDATORY) FBC SECTION 505 |
| | 12A) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3 |
| | |
| | 13) NEC 230.9(C) GROUND FAULT PERFORMANCE TESTING. THE |
| | GROUND-FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE |
| | TESTED WHEN FIRST INSTALLED ON SITE. |
| | |
| | 14) PROVIDE A LAYOUT OF ALL ELECTRICAL ROOMS INDICATING |
| | COMPLIANCE WITH NEC 110.26 FOR ABOUT ALL ELECTRICAL |
| | EQUIPMENT. |
| | |
| | 15) E605 INDICATE THE LOAD CALCULATION FOR PANEL |
| | NLGP1A. THE LOAD CALCULATION IS CUT OFF BY PANEL |
| | NLGP1B. |
| | |
| | 16) CORRECT THE NAMING CONVENTION FOR THE ELECTRICAL |
| | SHEETS. THE ELECTRICAL SHEETS ARE NOT ALL TOGETHER. |
| | |
| | 17) CORRECT THE NAME OF PANEL RDPB. ON PAGE E005 IT IS |
| | NAMED RDPB BUT ON PG E001 IT IS NAMED RMDPB |
| | |
| | 18) E200A |
| | PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN |
| | UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE |
| | FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO |
| | REFERENCE FOR CLARIFICATION. |
| | 18A) POWER PLAN NOTE 6. CALLS FOR A 20AMP CIRCUIT FOR |
| | DRYER BOOSTER FANS. |
| | BOOSTER FANS ARE NOT APPROVED FOR USE IN WPB PER THE |
| | WPB FIRE DEPT LOCAL CODES AND AMENDMENTS. |
| | |
| | 19) E200B |
| | PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN |
| | UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE |
| | FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO |
| | REFERENCE FOR CLARIFICATION. |
| | |
| | 20) E200C |
| | CORRECT PLAN NOTE 1 TO PROVIDE AFCI CIRCUIT BREAKER ON |
| | ALL CIRCUITS WITHIN SLEEPING AREA TO READ ?ALL |
| | 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH |
| | CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT |
| | FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, |
| | LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS, |
| | CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE |
| | PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER, |
| | COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF |
| | THE BRANCH CIRCUIT.? PER NEC 210.12(B) |
| | 20A) ANYWHERE RECEPTACLES ARE INSTALLED WITHIN 6 FT OF |
| | THE SINK SHALL BE GFI PROTECTED. NEC 210.8(B)(5) |
| | |
| | 21) E202CPROVIDE A GFI WITHIN SIGHT OF MECHANICAL |
| | EQUIPMENT. NEC 210.63 SEE ALSO 210.8(A)(3). |
| | |
| | 22) E301A |
| | INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| | FBC 505.2 |
| | |
| | 23) E301B |
| | PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS. |
| | INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| | FBC 505.2 |
| | |
| | 24) E310B |
| | PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS. |
| | INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT. |
| | FBC 505.2 |
| | |
| | 25) E601 |
| | REVISE PANEL SCHEDULE AND LOAD CALCULATION. PANEL C2 |
| | INDICATES A 27KVA DEMAND LOAD AT ONLY 75AMPS. THIS |
| | SHOULD BE CLOSER TO 130AMPS. |
| | 23A) APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS |
| | REQUIRED. |
| | |
| | 26) E602 |
| | APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS REQUIRED |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING, |
| | LIGHTNING PROTECTION, GENERATORS. HOOD EXHAUST, FIRE |
| | ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, |
| | AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |