Plan Review Notes
Plan Review Notes For Permit 14120908
Permit Number 14120908
Review Stop Z
Sequence Number 3
Notes
Date Text
2015-07-31 11:56:22FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PLEASE CLARIFY IF THE RETAINING WALL IS INCLUDED AS
 PART OF THIS PERMIT. THE SITE AND CIVIL PLANS SHOW THE
 MAJORITY OF THE RETAINING WALL AREA AS "NOT INCLUDED".
 THE FOUNDATION PLAN SHOWS MOST OF THE WALL AS INCLUDED.
 PRESUMABLY THE BALANCE OF THE RETAINING WALL WOULD BE
 INCLUDED WITH THE TRADITIONS II PERMIT. WHY SPLIT UP
 THE RETAINING WALL AND NOT BUILD IT UNDER ITS OWN
 PERMIT?
  
 2) THE NEW RETAINING WALL IS SHOWN IN DIFFERENT
 LOCATIONS ON THE PLANS LISTED BELOW. PLEASE EXPLAIN WHY
 DIFFERING WALL LOCATIONS ARE SHOWN.
  
 SHEET L101 COTLEUR & HEARING MASTER PLAN
 SHEET S-1.1 ONM&J FOUNDATION PLAN
 SHEET 1A DUNKELBERGER LAKE BANK RETAINING WALL LOCATION
 PLAN - OVERVIEW (IN THE RETAINING WALL OVERALL
 STABILITY EVALUATION REPORT)
 SHEET 1B DUNKELBERGER RETAINING WALL LOCATION PLAN -
 DETAILED (IN THE RETAINING WALL OVERALL STABILITY
 EVALUATION REPORT)
 SHEET 1C DUNKELBERGER RETAINING WALL LOCATION PLAN -
 DETAILED (IN THE RETAINING WALL OVERALL STABILITY
 EVALUATION REPORT)
  
 3) THE LANDSCAPE PLANS CALL FOR LITTORAL PLANTING TO
 THE WEST OF THE OVERLOOK PORTION OF THE RETAINING WALL.
 PLEASE EXPLAIN HOW THIS WILL OCCUR GIVEN THE DEPTH AND
 SLOPE THAT ARE BEING PROPOSED.
  
 4) THE IRRIGATION AND LANDSCAPING REQUIRE SEPARATE
 PERMIT SUBMITTALS, WITH PLANS. PLEASE NOT RESUBMIT
 THESE SHEETS.
  
 5) THE BUILDING FOOTPRINT MEETS ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  