| Date |
Text |
| 2015-07-27 15:10:39 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC |
| | SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS. |
| | MODEL D200E PROPOSED. PLEASE SEE FBC 715.4.2 ALLOWS UL |
| | 10B AS A TESTED STANDARD. SEE SPEC SHEETS PROVIDED; |
| | THIS DOOR APPEARS TO BE LIMITED TO 20 MINUTES , 45 |
| | MINUTES REQUIRED. |
| | |
| | THIS INFORMATION MAY BE SENT VIA EMAIL. |
| | |
| | ** IMPACT FEE PAYMENT REQUIRED (SEE IMPACT FEE REVIEW) |
| | **SEE THRESHOLD REVIEW - AGREEMENT AND PLAN REQUIRED TO |
| | BE REVISED PRIOR TO PERMIT ISSUANCE |
| | |
| | PROVISO ITEMS: |
| | |
| | 1. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT |
| | COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF |
| | EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION |
| | DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING |
| | REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE |
| | SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE |
| | REQUIRED PRIOR TO CERTIFICATE OF COMPLETION. |
| | |
| | 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF |
| | WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126. |
| | |
| | THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT, |
| | WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE |
| | PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN |
| | AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO |
| | DOCUMENT THE PERMIT FILE. |
| | |
| | 3. SHEET A101 SHOWS A PROPOSED FUTURE 2 HOUR FIRE DOOR. |
| | SEE FBC TABLE 715.4, A 3 HOUR FIRE DOOR IS REQUIRED FOR |
| | A 3 HOUR FIRE WALL. |
| | |
| | 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR |
| | TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107, |
| | FBC 1609 (SUBMITTAL, NO FEE). |
| | |
| | 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS |
| | AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE |
| | PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT |
| | APPLICATIONS, PLANS AND REVIEWS. |
| | |
| | 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT |
| | REVIEWED. |
| | |
| | 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL |
| | ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD |
| | INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED |
| | TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE |
| | REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE |
| | APPROVED THROUGH PLAN REVIEW PRIOR TO INSTALLATION. |
| | |
| | 8. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED |
| | FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS, |
| | STRUCTURAL FRAME, FBC TABLE 601. THE ROOF WAS SPECIFIED |
| | BUT NOT THE OTHER STRUCTURAL ELEMENTS. |
| | |
| | 9. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A |
| | CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC |
| | ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF |
| | APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE |
| | EXIT HARDWARE, FBC 1008.1.10. SPEC SHEETS WERE |
| | SUBMITTED BUT CONTAINED INFORMATION NOT CODE RELATED |
| | (FINISHES, HINGES, KICK PLATES, ETC.). SPEC BOOKS |
| | CANNOT BE USED IN LIEU OF PLANS TO SHOW CODE COMPLIANCE |
| | DUE TO THE LARGE AMOUNT OF INFORMATION NOT RELEVANT TO |
| | CODE COMPLIANCE, FBC 107. |
| | |
| | 10. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND |
| | FLOORS. |
| | |
| | 11. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH |
| | THIS SECTION. |
| | |
| | 12. TESTED ASSEMBLIES OR CALCULATED FIRE RESISTANCE |
| | DETAILS REQUIRED FOR ALL ELEMENTS REQUIRED TO BE RATED |
| | PER FBC TABLE 601. SUBMIT DETAILS PRIOR TO |
| | INSTALLATION. |
| | |