Text |
| 2015-04-04 06:41:19 | 1) THE PERMIT APPLICATION IS FOR A FOUNDATION ONLY BUT |
| | THERE ARE ADDITIONAL PLUMBING PLANS IN THE SET FOR WHAT |
| | APPEARS TO BE MOST OF THE PLUMBING. I UNDERSTAND THE |
| | REASONING FOR THIS BUT SINCE THE PERMIT IS FOR THE |
| | FOUNDATION ONLY, SUBMIT ONLY THE PLUMBINHG PLANS THAT |
| | ARE RELEVANT TO THE INSTALLATION OF THE UNDERGROUND |
| | PLUMBING. INCLUDE CONDENSATE, SANITARY, STORM, DOMESTIC |
| | WATER, GAS, ETC. WPB AMEND. TO 2010 FBC SEC. |
| | 107.3.5.1.3. |
| | 2) SUBMIT A SLAB REPAIR DETAIL FOR THE CONCRETE SLAB |
| | THAT IS TO BE CUT TO INSTALL THE PLUMBING.WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1. |
| | 3) SHT.P501 - AS DRAWN, THE SANITARY RISER DIAGRAM DOES |
| | NOT COMPLY WITH THE 2010 FPC SEC.909.1 FOR A HORIZONTAL |
| | WET VENT AND THE TYPE OF FIXTURES AND DRAINAGE FIXTURE |
| | UNIT LOAD PERMITTED PER TABLE 909.3. |
| | 4) SHT. P501 - SIZE ALL SECTIONS OF THE SANITARY RISER |
| | DIAGRAM WHEN PLANS ARE RESUBMITTED.WPB AMEND. TO 2010 |
| | FBC SEC. 107.3.5.1.3. |
| | |
| | THE FOLLOWING ADDITIONAL PLUMBING COMMENTS WILL APPLY |
| | WHEN THE ENTIRE PLAN IS SUBMITTED FOR THE MASTER |
| | PERMIT: |
| | |
| | ADDITIONAL COMMENTS |
| | 4) SHT. A101 - ENLARGED TOILET ROOM DETAIL #3 (ROOM |
| | #111 ) - THE DOOR APPEARS TO SWING INTO THE CLEAR FLOOR |
| | SPACE FOR THE LAVATORY IN TOILET ROOM #111. COMPLY WITH |
| | THE 2010 FAC SEC.603.2.3.( SEE EXCEPTIONS). |
| | 5) SHT. A103 - ROOF DRAIN RISER - 1/2 OF THE AREA OF |
| | ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF |
| | SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR INCLUSION |
| | IN CALCULATING VERTICAL CONDUCTORS, LEADERS AND |
| | HORIZONTAL STORM DRAINAGE PIPING. 2010 FPC SEC.1106.4. |
| | 6) SHT. A503 - ROOF SCUPPER DETAIL - SUPPLY THE LENGTH |
| | DIMENSION OF THE SCUPPER. THE DESIGN OF THE SCUPPER |
| | SHALL COMPLY W/ 2010 FPC TABLE 1106.7.THE PLAN NOTES |
| | THE SCUPPER IS DESIGNED PER SMACNA. CLARIFY.SEE 2010 |
| | FBC SECS 1503.4 THROUGH 1503.4.2.1. |
| | 7) SHT. A103 - THE AREAS OF THE SLOPED ROOFS THAT ARE |
| | DISCHARGING RAINWATER ONTO THE FLAT ROOFS SHALL ALSO BE |
| | ADDED INTO THE ROOF DRAINAGE CALCULATIONS. SUBMIT |
| | COMPLETE ROOF DRAINAGE CALCULATIONS THAT INCLUDE THE |
| | AREA OF THE PARAPET WALL AND ALSO THE SLOPED |
| | ROOFS.SUBMIT A COMPLETE STORMWATER RISER DIAGRAM FOR |
| | REVIEW. |
| | 8) SHT.P001 - THE ACCESSIBLE DRINKING FOUNTAIN/COOLER |
| | IS LISTED AS A SINGLE LEVEL. TWO ARE REQUIRED PER THE |
| | FAC SEC.211.2. CLARIFY. |
| | 9) SUBMIT FIRESTOPPING DETAILS FOR ALL FLOOR AND WALL |
| | PIPING PENETRATIONS. 2010 FBC SEC. 713. |
| | 10) TWO COPIE OF COMPLETE SETS OF PLANS SHALL BE |
| | SUBMITTED WITH ALL SHEETS LISTED ON SHT.G 000 INCLUDING |
| | THE "KES " DRAWINGS REFERRED TO ON SHT. P100. |
| | 11) SUBMIT A SLAB REPAIR DETAIL FOR WHERE THE SLAB IS |
| | TO BE CUT TO INSTALL ANY UNDERGROUND PLUMBING. WPB |
| | AMEND. TO 2010 FBC SEC.107.2.1. |
| | 12) SHT. P100 - SIZE ALL SECTIONS OF THE STORMWATER |
| | DRAINAGE SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 13) THE DRINKING FOUNTAIN IN VESTIBULE #113 APPEARS TO |
| | VIOLATE SEC.307.1 FOR PROTRUSION LIMITS. CLARIFY. |
| | CLEARLY SHOW THE REQUIRED 30" X 48" CLEAR FLOOR SPACE |
| | FOR THE DRINKING FOUNTAIN. FAC SEC.305, 602. |
| | 14) ALL HOSE BIBBS/WALL HYDRANTS SHALL BE VALVED PER |
| | THE FPC SEC.606.2. |
| | 15) SUBMIT DETAILS/PIPING DIAGRAM FOR THE WATER |
| | FILTRATION SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 16) THE WATER SUPPLY TO BEVERAGE DISPENSERS SHALL BE |
| | PROTECTED AGAINST BACKFLOW PER THE FPC SEC.608.16.1. |
| | COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS |
| | SHALL BE PROTECTED AGAINST BACKFLOW PER THE FPC |
| | SEC.608.16.10. |
| | 17) SUBMIT PLANS AND A GAS RISER DIAGRAM FOR ALL GAS |
| | PIPING TO BE INSTALLED. WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1. |
| | 18) SUBMIT A COMPLETE WATER RISER DIAGRAM FOR ALL NEW |
| | WATER PIPNG THAT IS GOING TO BE INSTALLED. |
| | 19) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |