2015-04-04 06:41:191) THE PERMIT APPLICATION IS FOR A FOUNDATION ONLY BUT
 THERE ARE ADDITIONAL PLUMBING PLANS IN THE SET FOR WHAT
 APPEARS TO BE MOST OF THE PLUMBING. I UNDERSTAND THE
 REASONING FOR THIS BUT SINCE THE PERMIT IS FOR THE
 FOUNDATION ONLY, SUBMIT ONLY THE PLUMBINHG PLANS THAT
 ARE RELEVANT TO THE INSTALLATION OF THE UNDERGROUND
 PLUMBING. INCLUDE CONDENSATE, SANITARY, STORM, DOMESTIC
 WATER, GAS, ETC. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 2) SUBMIT A SLAB REPAIR DETAIL FOR THE CONCRETE SLAB
 THAT IS TO BE CUT TO INSTALL THE PLUMBING.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) SHT.P501 - AS DRAWN, THE SANITARY RISER DIAGRAM DOES
 NOT COMPLY WITH THE 2010 FPC SEC.909.1 FOR A HORIZONTAL
 WET VENT AND THE TYPE OF FIXTURES AND DRAINAGE FIXTURE
 UNIT LOAD PERMITTED PER TABLE 909.3.
 4) SHT. P501 - SIZE ALL SECTIONS OF THE SANITARY RISER
 DIAGRAM WHEN PLANS ARE RESUBMITTED.WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
  
 THE FOLLOWING ADDITIONAL PLUMBING COMMENTS WILL APPLY
 WHEN THE ENTIRE PLAN IS SUBMITTED FOR THE MASTER
 PERMIT:
  
 ADDITIONAL COMMENTS
 4) SHT. A101 - ENLARGED TOILET ROOM DETAIL #3 (ROOM
 #111 ) - THE DOOR APPEARS TO SWING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY IN TOILET ROOM #111. COMPLY WITH
 THE 2010 FAC SEC.603.2.3.( SEE EXCEPTIONS).
 5) SHT. A103 - ROOF DRAIN RISER - 1/2 OF THE AREA OF
 ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR INCLUSION
 IN CALCULATING VERTICAL CONDUCTORS, LEADERS AND
 HORIZONTAL STORM DRAINAGE PIPING. 2010 FPC SEC.1106.4.
 6) SHT. A503 - ROOF SCUPPER DETAIL - SUPPLY THE LENGTH
 DIMENSION OF THE SCUPPER. THE DESIGN OF THE SCUPPER
 SHALL COMPLY W/ 2010 FPC TABLE 1106.7.THE PLAN NOTES
 THE SCUPPER IS DESIGNED PER SMACNA. CLARIFY.SEE 2010
 FBC SECS 1503.4 THROUGH 1503.4.2.1.
 7) SHT. A103 - THE AREAS OF THE SLOPED ROOFS THAT ARE
 DISCHARGING RAINWATER ONTO THE FLAT ROOFS SHALL ALSO BE
 ADDED INTO THE ROOF DRAINAGE CALCULATIONS. SUBMIT
 COMPLETE ROOF DRAINAGE CALCULATIONS THAT INCLUDE THE
 AREA OF THE PARAPET WALL AND ALSO THE SLOPED
 ROOFS.SUBMIT A COMPLETE STORMWATER RISER DIAGRAM FOR
 REVIEW.
 8) SHT.P001 - THE ACCESSIBLE DRINKING FOUNTAIN/COOLER
 IS LISTED AS A SINGLE LEVEL. TWO ARE REQUIRED PER THE
 FAC SEC.211.2. CLARIFY.
 9) SUBMIT FIRESTOPPING DETAILS FOR ALL FLOOR AND WALL
 PIPING PENETRATIONS. 2010 FBC SEC. 713.
 10) TWO COPIE OF COMPLETE SETS OF PLANS SHALL BE
 SUBMITTED WITH ALL SHEETS LISTED ON SHT.G 000 INCLUDING
 THE "KES " DRAWINGS REFERRED TO ON SHT. P100.
 11) SUBMIT A SLAB REPAIR DETAIL FOR WHERE THE SLAB IS
 TO BE CUT TO INSTALL ANY UNDERGROUND PLUMBING. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHT. P100 - SIZE ALL SECTIONS OF THE STORMWATER
 DRAINAGE SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 13) THE DRINKING FOUNTAIN IN VESTIBULE #113 APPEARS TO
 VIOLATE SEC.307.1 FOR PROTRUSION LIMITS. CLARIFY.
 CLEARLY SHOW THE REQUIRED 30" X 48" CLEAR FLOOR SPACE
 FOR THE DRINKING FOUNTAIN. FAC SEC.305, 602.
 14) ALL HOSE BIBBS/WALL HYDRANTS SHALL BE VALVED PER
 THE FPC SEC.606.2.
 15) SUBMIT DETAILS/PIPING DIAGRAM FOR THE WATER
 FILTRATION SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 16) THE WATER SUPPLY TO BEVERAGE DISPENSERS SHALL BE
 PROTECTED AGAINST BACKFLOW PER THE FPC SEC.608.16.1.
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER THE FPC
 SEC.608.16.10.
 17) SUBMIT PLANS AND A GAS RISER DIAGRAM FOR ALL GAS
 PIPING TO BE INSTALLED. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 18) SUBMIT A COMPLETE WATER RISER DIAGRAM FOR ALL NEW
 WATER PIPNG THAT IS GOING TO BE INSTALLED.
 19) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  