Notes
Date Text
2015-07-13 20:41:46ELECTRICAL PROVISO FOR PERMIT 14120907
  
 HEATING AS DESCRIBED ON PLANS IS NOT COMPLIANT
 CORRECT ACCORDINGLY:
 R303.8 REQUIRED HEATING. WHEN THE WINTER DESIGN
 TEMPERATURE IN TABLE R301.2(1) IS BELOW 60?F (16?C),
 EVERY DWELLING UNIT SHALL BE PROVIDED WITH HEATING
 FACILITIES CAPABLE OF MAINTAINING A MINIMUM ROOM
 TEMPERATURE OF 68?F (20?C) AT A POINT 3 FEET (914 MM)
 ABOVE THE FLOOR AND 2 FEET (610 MM) FROM EXTERIOR WALLS
 IN ALL HABITABLE ROOMS AT THE DESIGN TEMPERATURE. THE
 INSTALLATION OF ONE OR MORE PORTABLE SPACE HEATERS
 SHALL NOT BE USED TO ACHIEVE COMPLIANCE WITH THIS
 SECTION.
  