| Plan Review Notes For Permit 14120907 |
| Permit Number |
14120907 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-26 19:49:51 | SECOND ELECTRICAL REVIEW FAILED AS MENTIONED BELOW: | | | BOTH NEC & FBC HAVE MINIMUM REQUIREMENTS THAT SHALL BE | | | COMPLIED WITH AND ARE NOT REFLECTED ON THE SUBMITTED | | | DRAWINGS. | | | 1. FBC-R 303, REQUIRES THAT YOU PROVIDE HEAT | | | 2. FBC-R 306, REQUIRES THAT YOU HAVE HOT WATER AND | | | THOUGH INDICATED IN THE PANEL SCHEDULE, A WATER HEATER | | | IS NOT INDICATED ON THE PLANS. | | | 3. THE PANEL SCHEDULE REFLECTS THE REQUIRED LAUNDRY | | | CIRCUIT, BUT THE DRAWING DOES NOT. | | | 4. THE PANEL SCHEDULE REFLECTS AN AHU & A CU AS WELL, | | | BUT THEY ARE NOT INDICATED ON THE DRAWINGS. | | | 5. THE PANEL SCHEDULE REFLECTS AN ELECTRIC OVEN, BUT | | | NOT AN ELECTRIC RANGE, YET THE DRAWING INDICATES A | | | RANGE AND NO OVEN. CLARIFY IF THEY ARE ONE OF THE SAME. | | | IF NOT AND THE RANGE IS A GAS APPLIANCE, AS PER FBC-R | | | 315, CARBON MONOXIDE DETECTION IS REQUIRED. | | | 6 OUTLET PLACEMENT SHALL BE AS INDICATED BY NEC 210.52, | | | CHECK THE DENIED PLAN FOR ASSISTANCE WITH OUTLET | | | PLACEMENT. | | | | | | CORRECT THE ELECTRICAL SUBMITTAL AS INDICATED ABOVE. | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CALL ME, I CAN BE REACHED BY CALLING MIKE AT | | | 561-805-6743 |
|