2015-02-02 16:03:50PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE ZONING REVIEW STATES THAT A TWO UNIT DWELLING IS
 NOT ALLOWED.
  
 1) SUBMIT AN ELECTRICAL RISER DIAGRAM WITH WIRE SIZES,
 CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN.FOR A SINGLE FAMILY DWELLING. FBC 107.3.5.3
  
 2) SUBMIT A PANEL SCHEDULE FOR A SINGLE FAMILY
 DWELLING. FBC 107.3.5.3
  
 3) SUBMIT ELECTRICAL LOAD CALCULATIONS FOR A SINGLE
 FAMILY DWELLING. NEC 220.40
  
 4) REVISE THE FLOOR PLAN TO A SINGLE FAMILY DWELLING.
 FBC 107.2.1
  
 5) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 6) NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
  
 7) NEC 210.8 (A)(6) RECEPTACLES SERVING COUNTERTOP
 SURFACES ARE REQUIRED TO BE GFCI PROTECTED.
  
 8) NEC 210.52 (E)(1) ? AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED
 NOT MORE THAN 6 ? FT. ABOVE GRADE SHALL BE INSTALLED AT
 THE FRONT AND BACK OF THE DWELLING.
  
 9) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE
 PRESENT.
  
 10) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 11) NEC 210.12 (B) ? OUTLETS ARE REQUIRED TO BE AFCI
 PROTECTED.
  
 12) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE
 REQUIRED.