| 2015-01-12 12:59:15 | 1/12/2015 |
| | PROJECT: EARTHLINK |
| | PERMIT#: 14120886 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) FBC- 107.3.5.3. PROVIDE A DETAILED ELECTRICAL |
| | SERVICE DISTRIBUTION SYSTEM TO INCLUDE THE FOLLOWING: A |
| | RISER DIAGRAM WITH A GROUNDING ELECTRODE SYSTEM, ALL |
| | SERVICE DISCONNECTS, AND PANELS, ALL CONDUIT AND WIRE |
| | SIZES, A COMPLETE DETAILED LOAD CALCULATION(S), CLEAR |
| | AND SPECIFIC PANEL DIRECTORIES, AND ALL CIRCUIT NUMBERS |
| | AS INDICATED ON THE PANEL DIRECTORIES TO BE SHOWN ON |
| | THE ELECTRICAL FLOOR, AND CELING LIGHTING PLANS. THE |
| | RISER DIAGRAM SUBMITTED IS INCOMPLETE.INDICATE AND |
| | INCLUDE ON THE REVISED RISER DIAGRAM ALL UTILITY |
| | SERVICE ENTRANCE CONDUIT AND WIRE SIZES, MAIN |
| | DISCONNECTS, PANELS, FEEDERS, AND GROUNDING ELECTRODE |
| | SYSTEM ASSOCIATED WITH THE SUITE UNDER CONSTRUCTION |
| | ONLY. INDICATE AND DISDINGUISH BETWEEN WHAT IS EXISTING |
| | TO REMAIL, WHAT IS EXISTING TO BE RELOCATED, AND WHAT |
| | IS PROPOSED TO BE NEW. WITH THE LOAD CALCULATION |
| | INDICATE WHAT IS THE EXISTING LOAD AND WHAT IS PROPOSED |
| | TO BE ADDED, AND THE NEW TOTAL CONNECTED LOAD. |
| | |
| | 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16, 110.22 |
| | |
| | 4) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| | EACH OF THE ELECTRICAL PANELS. FOR THE PANEL THAT IS |
| | BEING RELOCATED, PROVIDE BOTH THE OLD EXISTING LOCATION |
| | AND THE NEW RELOACTED LOCATION ON THE ELECTRICAL FLOOR |
| | PLAN. |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FIRE ALARM, |
| | ACCESS CONTROL SYSTEM, SECURITY, CCTV, NETWORK, DATA, |
| | AND, COMMUNICATION AS NEEDED. NOT ALL MAY BE UTILIZED |
| | OR RQUIRED ON THIS PROJECT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |