| Plan Review Notes For Permit 14120864 |
| Permit Number |
14120864 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-01-13 12:15:42 | | | | 14120864 | | | 1101 S. FLAGLER | | | SITE LIGHTING ELECTRIC | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS. | | | | | | PROVIDE THE SPECIFICATIONS FOR THE LIGHTING POLES AND | | | FIXTURES. PROVIDE SIGNED AND SEALED WIND LOADING | | | CERTIFICATION FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES | | | FROM THE ENGINEER OF RECORD. NEC 110.2, FBC 1609.1, | | | ASCE 7-10 | | | | | | ROBERT LECKY, CBO | | | ELECTRICAL PLANS REVIEW | | | 561-373-3701 | | | [email protected] | | | | | | |
|