Plan Review Notes
Plan Review Notes For Permit 14120834
Permit Number 14120834
Review Stop B
Sequence Number 2
Notes
Date Text
2015-06-29 08:46:022ND REVIEW: FBC 2010
  
 THE FOLLOWING COMMENTS ARE FROM THE FIRST REVIEW AND
 HAVE NOT BEEN ADEQUATELY ADDRESSED:
 FBC 107. THE PLANS DO NOT HAVE ADEQUATE DETAIL
 DEPICTING THE MWFRS. MISSING INFORMATION INCLUDES BUT
 IS NOT LIMITED TO, ROOF SHEATHING NAILING, BEAM
 CONSTRUCTION, BEAM TO COLUMN CONNECTION.
  
 A STRUCTURAL ENGINEER SHOULD EVALUATE THE PLAN AND
 PROVIDE A NEW STRUCTURAL PLAN. PLEASE PROVIDE DESIGN
 PRESSURES, AND EVALUATE THE DESIGN FOR UPLIFT
 RESISTANCE, JOIST & BEAM SPANS, LIVE LOADS AND DEAD
 LOADS LATERAL FORCES AT CONECTIONS PURSUANT TO FBC-R
 CHAPTERS 3 & 8.
  
 AS FOR THE ROOFING MATERIAL, ADEQUATE INFORMATION HAS
 NOT BEEN PROVIDED AS FOLLOWS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 THE PRODUCT PROVIDED NOA 14-0611.01 REQUIRES
 CALCULATION PER LIMITAION #7, SUCH CALCULATIONS SHALL
 BE PREPARED BY A FLORIDA LICENSED ENGINEER.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  