2 |
|
| Notes |
| Date |
Text |
| 2015-06-29 08:46:02 | 2ND REVIEW: FBC 2010 | | | | | | THE FOLLOWING COMMENTS ARE FROM THE FIRST REVIEW AND | | | HAVE NOT BEEN ADEQUATELY ADDRESSED: | | | FBC 107. THE PLANS DO NOT HAVE ADEQUATE DETAIL | | | DEPICTING THE MWFRS. MISSING INFORMATION INCLUDES BUT | | | IS NOT LIMITED TO, ROOF SHEATHING NAILING, BEAM | | | CONSTRUCTION, BEAM TO COLUMN CONNECTION. | | | | | | A STRUCTURAL ENGINEER SHOULD EVALUATE THE PLAN AND | | | PROVIDE A NEW STRUCTURAL PLAN. PLEASE PROVIDE DESIGN | | | PRESSURES, AND EVALUATE THE DESIGN FOR UPLIFT | | | RESISTANCE, JOIST & BEAM SPANS, LIVE LOADS AND DEAD | | | LOADS LATERAL FORCES AT CONECTIONS PURSUANT TO FBC-R | | | CHAPTERS 3 & 8. | | | | | | AS FOR THE ROOFING MATERIAL, ADEQUATE INFORMATION HAS | | | NOT BEEN PROVIDED AS FOLLOWS. | | | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | THE PRODUCT PROVIDED NOA 14-0611.01 REQUIRES | | | CALCULATION PER LIMITAION #7, SUCH CALCULATIONS SHALL | | | BE PREPARED BY A FLORIDA LICENSED ENGINEER. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|