| Plan Review Notes For Permit 14120834 |
| Permit Number |
14120834 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-21 09:02:59 | 1ST REVIEW: FBC 2010 | | | | | | FBC 107. THE PLANS DO NOT HAVE ADEQUATE DETAIL | | | DEPICTING THE MWFRS. MISSING INFORMATION INCLUDES BUT | | | IS NOT LIMITED TO, ROOF SHEATHING NAILING, BEAM | | | CONSTRUCTION, BEAM TO COLUMN CONNECTION, COLUMN | | | REINFORCEMENT, ROOF FRAMING MEMBER TYPE. ELEVATIONS | | | INDICATE A GABLE ROOF, ROOFING NOTES INDICATE A FLAT | | | ROOF. A STRUCTURAL ENGINEER SHOULD EVALUATE THE PLAN | | | AND PROVIDE A NEW STRUCTURAL PLAN. | | | | | | TWO SETS OF PLANS ARE REQUIRED. | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|