 PROJECT: FLAGLER SOUTH RESIDENCE
 PERMIT#: 14120822
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE BASIC ELMENTS OF ELECTRICAL DEMOLITION TO
 INCLUDE THE FOLLOWING:
  
 1) THE LOCATION OF THE ELECTRICAL SERVICE,
 DISCONNECT(S), AND PANEL(S).
 2) LOCATION AND SOURCE OF TEMPORARY POWER FOR
 DEMOLITION/RENNOVATION.
 3) DETAIL OF LIGHTING AFFECTED BY DEMOLITION. INCLUDE
 LIGHTING AND SWITCHES THAT WILL REMIAN AND LIGHTING AND
 SWITCHES THAT WILL BE REMOVED TO INCLUDE THE SAFE
 TERMINATION OF DEMOLISHED CIRCUITRY BACK TO THE NEAREST
 SOURCE.
 4) PROVIDE THE SAME DETAILS FOR THE SAFE REMOVAL
 RECEPTACLE OUTLETS, MECHANICAL EQUIPMENT, WATER HEATER,
 APPLIANCES AND CIRCUITRY AFFECTED BY DEMOLITION AND THE
 TERMINATION OF CIRCUITRY BACK TO THE NEAREST SOURCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  