| Plan Review Notes For Permit 14120816 |
| Permit Number |
14120816 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-03-27 05:30:02 | 1) SHOW ON THE SITE PLAN HOW WATER AND SEWER WILL BE | | | BROUGHT TO THIS BUILDING. SHOW THE WATER AND SEWER | | | LINES ON THE SITE PLAN AND SHOW THE SIZES OF EACH LINE. | | | WPB AMEND. TO 2010 FBC SEC.107.2.1.2ND REQUEST. | | | 2) A MINIMUM OF A DOUBLE CHECK VALVE BACKFLOW PREVENTER | | | SHALL BE INSTALLED ON THE WATER SERVICE AT THE METER IN | | | ACCORDANCE WITH THE CWPB CROSS CONNECTION MANUAL. SHOW | | | THE LOCATION OF THE BFP DEVICE & METER ON THE SITE | | | PLAN. 2ND REQUEST. | | | 3) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER | | | THE 2010 FL. ACCESSIBILITY CODE SEC.211.2. ONLY ONE | | | DRINKING FOUNTAIN IS SHOWN. 2ND REQUEST. | | | 4) THE DESCRIPTION OF WORK ON THE PLUMBING APPLICATION | | | REFERS TO A MINI LIFT STATION. SUBMIT MANUFACTURER'S | | | SPECS ON THE LIFT STATION ( PUMPS & BASIN ) AND A | | | PIPING DIAGRAM FOR ALL PIPING. SHOW THE LOCATION OF THE | | | LIFT STATION ON THE SITE PLAN, WPB AMEND. TO 2010 FBC | | | SEC.107.2.1. SUMP, EJECTOR AND PIPING SHALL COMPLY W/ | | | 2010 FPC SEC. 712.1, 712.2, 712.3.2, 712.3.5, 712.4.2, | | | 916.5 & 916.5.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|