| 2015-01-04 06:02:10 | 1) SHOW ON THE SITE PLAN HOW SEWER AND WATER WILL BE | | | BROUGHT TO THIS BUILDING. WPB AMENDMENTS TO 2010 FBC | | | SEC.107.2.1. | | | 2) SUBMIT DOCUMENTATTION THAT THE SUBMITTED PLANS HAVE | | | BEEN REVIEWED AND APPROVED BY A AN AGENCY AUTHORIZED TO | | | PERFORM PLAN REVIEW IN ACCORDANCE WITH FL. ADMIN. CODE | | | RULE 9B-1, FL. STATUTE 553.37 & THE 2010 FBC | | | SEC.428.4.2 AND THAT THEY COMPLY WITH THE 2010 FBC PER | | | THE 2010 FBC SEC.428.4.1. | | | 3) A MINIMUM OF A DOUBLE CHECK VALVE BACKFLOW | | | PREVENTION DEVICE SHALL BE INSTALLED ON THE WATER | | | SERVICE NEAR THE SOURCE PER THE CWPB CROSS CONNECTION | | | ORDINANCE. | | | 4) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER | | | THE 2010 FL. ACCESSIBILITY CODE SEC. 211.2. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|