Plan Review Notes
Plan Review Notes For Permit 14120816
Permit Number 14120816
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-09 17:15:59BUILDING PLAN REVIEW
 PERMIT: 14120816
 ADD: 8100 IBIS BLVD
 CONT: RIGHT ANGLE CONSTRUCTION
 TEL: (561)313-3301
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRI. JAN. 09/2015
 ACTION: DENIED
  
 1)SHEET C1 OF 1 NOTES 22 & 23 MAKE THIS PLAN APPEAR TO
 BE A STATE APPROVED BUILDING UNDER THE MODULAR BUILDING
 PROGRAM. CONCRETE MODULAR SYSTEMS DOES NOT HAVE THIS
 MODEL LISTED AS STATE APPROVED NOR DOES IT LIST A STATE
 PLAN REVIEW APPROVAL. THE ENGINEER OF RECORD WILL HAVE
 TO SIGN AND DATE EACH PAGE OF HE PLANS AND THE COVER
 SHEET OF CALCULATION WITH INDEX SHEET WILL ALSO NEED TO
 BE SIGNED AND DATED.
  
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 ((C) WALL LOUVERS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (F) SKYLIGHTS WILL NEED TO MEET LARGE MISSILE IMPACT
 TESTING.
  
 3) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 4) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 5) STRUCTURAL CALCULATIONS FOR B1798 SHOW V 140 MPH, IS
 THIS VULT OR VASD? THE PRESSURES WILL VARY GREATLY.IT
 APPEARS THE BUILDING CATEGORY IS DESIGNED AS A II WHICH
 WOULD REFLECT A 140 MPH VASD, PLEASE VERIFY ON PLANS.
  
 6) SKYLIGHT DETAIL SHEET D1 OF 1 NEEDS TO BE UPDATED IN
 DESIGN TO THE 2010 FBC-B ASCE 7-10.
  
 7) SHEET C1 OF 1 ALSO INDICATES A SINGLE WATER FOUNTAIN
 PLEASE SHOW CONFORMANCE WITH 2010 FBC-ACCESSIBILITY
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 8) NO SOILS REPORT WAS SUBMITTED SHOWING HOW THE
 MINIMUM SAFE BEARING VALUE OF 2000 PSF WILL BE
 ACHIEVED. 2010 FBC-B 1803.5.2.
  
 9) SHEET S1 NOTE 2 INDICATES SEE SHEET 3 FOR
 FOUNDATION. SHEET 3 INDICATES FLOOR SLAB DESIGN IS
 BASED ON A FOUNDATION SYSTEM (PROVIDED BY OTHERS), NO
 FOUNDATION DESIGN WAS PROVIDED. 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS 107.3.5.1.1 (8) FOUNDATIONS .
  
 10) 2010 FBC-B 1809.4 DEPTH AND WIDTH OF FOOTINGS. THE
 MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED GROUND
 SURFACE SHALL BE 12 INCHES (305 MM). WHERE APPLICABLE,
 THE REQUIREMENTS OF SECTION 1809.5 SHALL ALSO BE
 SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL BE 12
 INCHES (305 MM).
  
 11) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1816.1
 TERMITE PROTECTION.
  
 12) THE PLANS FAIL TO PROVIDE HOW THE BUILDING IS
 DESIGNED TO TRANSFER THE LOADS OF UPLIFT, LATERAL
 LOADS, FROM SLIDDING, MISSING TIE IN TO THE FOUNDATION,
 MAIN WIND FORCE RESISTING SYSTEM. 1609.6.4 DESIGN
 PROCEDURE. THE MWFRS AND THE COMPONENTS AND CLADDING OF
 EVERY BUILDING OR OTHER STRUCTURE SHALL BE DESIGNED FOR
 THE PRESSURES CALCULATED USING EQUATION 16-34.
  
 13) 1503.7 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS, OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 14) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 1203.4.1
 VENTILATION AREA REQUIRED. THE MINIMUM OPENABLE AREA TO
 THE OUTDOORS SHALL BE 4 PERCENT OF THE FLOOR AREA BEING
 VENTILATED.
  
 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  