2015-01-08 10:18:59BUILDING PLAN REVIEW
 REVISION: 14120788
 PERMIT: 13040466
 ADD: 1025 26TH ST
 CONT: AHRENS COMPANIES
 TEL: ( 772)260-2156
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 08/2015
 ACTION: DENIED
  
 1) THE SUBMITTED REVISION FOR A MODULAR BUILDING PLEASE
 REVIEW SHEETS :
 SHEET 100 EXISITNG SITE PLAN/ DEMOLITION PLAN. EXISITNG
 MODULAR BUILDING TO BE REMOVED AND REPLACED BY OWNER
 WITH A NEW MODULAR BUILDING.
 SHEET 101 NOTE: MODULAR OFFICE, STEPS & RAMP PER
 WILLIAM SCOTSMAN OR APPROVED SUBSTITUTE. SEPARATE
 PERMIT REQUIRED.
 NOTE A PERMIT APPLICATION WILL BE REQUIRED TO CHANGE
 THIS REVISION TO A PERMIT APPLICATION. FEES WILL BE
 ADDJUSTED.
  
 2) IT WILL BE ASSUMED THAT THIS UNIT IS GOING TO BE SET
 AS A LONG TERM, NOT TEMPARARY LESS THAN 180 DAYS. THEN
 THE FOUNDATIONS WILL NEED TO COMPLY WITH
 2010 FBC-B 1809.4 DEPTH AND WIDTH OF FOOTINGS.
 THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED
 GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE
 APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL
 ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL
 BE 12 INCHES (305 MM). SEE TABLE 1809.7 AND FOOTNOTE E
 FOR THE THICKNESS OF FOUNDATION WALLS SEE SECTION
 1807.1.6.
  
 3) THE STATE APPROVED PLANS INDICATE THE OCCUPANCY
 CLASSIFICATION AS A BUSINESS OCCUPANCY AND WIND DESIGN
 AS 150 VULT/ 116 VASD. THE WIND ZONE FOR THIS LOCATION
 FOR BUILDING CATEGORY II STRUCTURES IS 170VULT/ 132
 VASD. THIS UNIT WILL NOT BE ABLE TO BE PLACED IN THIS
 WIND ZONE. SEE THE 2010 FBC-B FIGURE 1609A.
  
 4) FOR THE NEW PLANS TO BE SUBMITTED REVIEW THE ITEMS
 TO BE SITE INSTALLED ITEMS:
 FOUNDATION,
 STAIRS, LANDINGS & RAMPS,
 GLAZING OPENING PROTECTION (STORM SHUTTERS)
 GUTTERS AND DOWNSPOTS
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  