| 2015-01-08 10:18:59 | BUILDING PLAN REVIEW |
| | REVISION: 14120788 |
| | PERMIT: 13040466 |
| | ADD: 1025 26TH ST |
| | CONT: AHRENS COMPANIES |
| | TEL: ( 772)260-2156 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JAN. 08/2015 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED REVISION FOR A MODULAR BUILDING PLEASE |
| | REVIEW SHEETS : |
| | SHEET 100 EXISITNG SITE PLAN/ DEMOLITION PLAN. EXISITNG |
| | MODULAR BUILDING TO BE REMOVED AND REPLACED BY OWNER |
| | WITH A NEW MODULAR BUILDING. |
| | SHEET 101 NOTE: MODULAR OFFICE, STEPS & RAMP PER |
| | WILLIAM SCOTSMAN OR APPROVED SUBSTITUTE. SEPARATE |
| | PERMIT REQUIRED. |
| | NOTE A PERMIT APPLICATION WILL BE REQUIRED TO CHANGE |
| | THIS REVISION TO A PERMIT APPLICATION. FEES WILL BE |
| | ADDJUSTED. |
| | |
| | 2) IT WILL BE ASSUMED THAT THIS UNIT IS GOING TO BE SET |
| | AS A LONG TERM, NOT TEMPARARY LESS THAN 180 DAYS. THEN |
| | THE FOUNDATIONS WILL NEED TO COMPLY WITH |
| | 2010 FBC-B 1809.4 DEPTH AND WIDTH OF FOOTINGS. |
| | THE MINIMUM DEPTH OF FOOTINGS BELOW THE UNDISTURBED |
| | GROUND SURFACE SHALL BE 12 INCHES (305 MM). WHERE |
| | APPLICABLE, THE REQUIREMENTS OF SECTION 1809.5 SHALL |
| | ALSO BE SATISFIED. THE MINIMUM WIDTH OF FOOTINGS SHALL |
| | BE 12 INCHES (305 MM). SEE TABLE 1809.7 AND FOOTNOTE E |
| | FOR THE THICKNESS OF FOUNDATION WALLS SEE SECTION |
| | 1807.1.6. |
| | |
| | 3) THE STATE APPROVED PLANS INDICATE THE OCCUPANCY |
| | CLASSIFICATION AS A BUSINESS OCCUPANCY AND WIND DESIGN |
| | AS 150 VULT/ 116 VASD. THE WIND ZONE FOR THIS LOCATION |
| | FOR BUILDING CATEGORY II STRUCTURES IS 170VULT/ 132 |
| | VASD. THIS UNIT WILL NOT BE ABLE TO BE PLACED IN THIS |
| | WIND ZONE. SEE THE 2010 FBC-B FIGURE 1609A. |
| | |
| | 4) FOR THE NEW PLANS TO BE SUBMITTED REVIEW THE ITEMS |
| | TO BE SITE INSTALLED ITEMS: |
| | FOUNDATION, |
| | STAIRS, LANDINGS & RAMPS, |
| | GLAZING OPENING PROTECTION (STORM SHUTTERS) |
| | GUTTERS AND DOWNSPOTS |
| | |
| | 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |