Notes
Date Text
2014-12-24 14:30:431) SUBMIT A WATER RISER FOR REVIEW PER WPB AMEND .TO
 2010 FBC SEC.107.3.5.3 (11).
 2) SHT. S 04 - OVERFLOW SCUPPERS SHALL BE LOCATED NO
 LESS THAN 2" NOR MORE THAN 4" ABOVE THE FINISHED ROOF
 PER 1020 FL. BLDG. CODE, RESIDENTIAL, SEC.903.4.1.
 3) A VENT IS REQD.BETWEEN THE SHOWER AND THE WATER
 CLOSET ON THE 2ND FLOOR. 2010 FBCR SEC,P3108.2.1.
 4) SHT.P.01 - SIZE ALL SECTIONS OF THE DRAINAGE PIPE ON
 THE RISER DIAGRAM.
  