| 2015-02-04 10:02:35 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY ELECTRICAL |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY |
| | SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | 2) SHOW COMPLIANCE WITH FBC-R314 FOR REQUIRED SMOKE |
| | ALARMS. |
| | |
| | 3) SHOW LOCATION OF A/C EQUIPMENT AND THEIR DISCONNECTS |
| | ON THE ELECTRICAL PLANS. FBC 107.2.1 |
| | |
| | 4) NEC 210.63 - PROVIDE A GFCI PROTECTED SERVICE OUTLET |
| | FOR WITHIN 25' OF MECHANICAL EQUIPMENT. |
| | |
| | 5) NEC 210.8 (A) (1)-(8) - GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION REQUIRED. ALL |
| | RECEPTACLES LOCATED IN THE GARAGE ARE REQUIRED TO BE |
| | GFCI PROTECTED. |
| | |
| | 6) NEC 210.12 (B) - OUTLETS ARE REQUIRED TO BE AFCI |
| | PROTECTED. |
| | |
| | 7) NEC 406.11 - TAMPER-RESISTANT RECEPTACLES ARE |
| | REQUIRED. |
| | |
| | 8) NEC 210.52 (E)(1) - AT LEAST ONE RECEPTACLE OUTLET |
| | ACCESSIBLE WHILE STANDING AT GRADE LEVEL AND LOCATED |
| | NOT MORE THAN 6 1/5 FT. ABOVE GRADE SHALL BE INSTALLED |
| | AT THE FRONT AND BACK OF THE DWELLING. |
| | |
| | 9) NEC 210.70 (A) - (C) LIGHTING OUTLETS REQUIRED. AT |
| | LEAST ONE WALL SWITCH CONTROLLED LIGHTING OUTLET IS |
| | REQUIRED ON THE EXTERIOR SIDE OF OUTDOOR ENTRANCES OR |
| | EXITS. |
| | |
| | 10) NEC 250.50 - BOND ALL GROUNDING ELECTRODES THAT ARE |
| | PRESENT. NEC 250.56 - SERVICE GROUNDING ELECTRODE TO BE |
| | AUGMENTED BY AN ADDITIONAL ELECTRODE 6 FEET AWAY OR |
| | PROVIDE EVIDENCE OF RESISTANCE TO GROUND OF 25 OHMS OR |
| | LESS. |
| | |
| | 11) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL |
| | BE PROVIDED. |
| | |
| | 12) IT APPEARS THAT YOUR CALCULATIONS FOR THE |
| | UNBALANCED NEUTRAL LOAD ARE INCORRECT. BASED ON YOUR |
| | CALCULATION RESULT OF 155 AMPS, THE 1/0 NEUTRAL FEEDER |
| | FROM THE METER TO PANEL A IS TOO SMALL. NEC 220.16 AND |
| | 220.61 |
| | |
| | |
| | |
| | |
| | |
| | |