| 2015-02-03 18:32:05 | PLAN REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) CLARIFY THE AREA DESCRIPTIONS ON SHEET A-01. THE |
| | FLOOR PLANS SHOW A GARAGE ON THE FIRST FLOOR AND AN |
| | APARTMENT ON THE SECOND FLOOR. THE AREA COMPUTATION |
| | LISTS THE FIRST FLOOR AS A CABANA AND THE SECOND FLOOR |
| | AS A PLAYROOM. PLEASE COORDINATE. FBC 107.2.1 |
| | |
| | 2) CLARIFY THE TYPE OF WINDOWS THAT WILL BE INSTALLED. |
| | THE WINDOW SCHEDULE ON A-01 SPECIFY SH (SINGLE HUNG). |
| | THE NOTES BELOW THE WINDOW SCHEDULE STATE ALL WINDOWS |
| | TO BE CASEMENT AND FIXED BY T&M WINDOWS. THE WINDOW |
| | PRODUCT APPROVAL IS FOR PGT DOUBLE HUNG WINDOWS. FBC |
| | 107.2.1 |
| | |
| | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. PROVIDE SUBMITTALS FOR THE 8' WIDE |
| | DOUBLE OUTSWING GARAGE DOORS. |
| | |
| | 4) FBC-R318.6 ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST |
| | 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| | WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR |
| | SPLASH BLOCKS. |
| | |
| | 5) FBC-R311.7.7.1 HANDRAIL HEIGHT, MEASURED VERTICALLY |
| | FROM THE SLOPED PLANE ADJOINING THE TREAD NOSING, OR |
| | FINISH SURFACE OF RAMP SLOPE, SHALL BE NOT LESS THAN 34 |
| | INCHES AND NOT MORE THAN 38 INCHES. |
| | |
| | 6) FBC-R704 IN ORDER TO PROVIDE FOR INSPECTION FOR |
| | TERMITE INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL |
| | COVERINGS AND FINAL EARTH GRADE ON THE EXTERIOR OF A |
| | BUILDING SHALL NOT BE LESS THAN 6 INCHES EXCEPTIONS: 1. |
| | PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS THAN 5/8 |
| | INCH THICK ADHERED DIRECTLY TO THE MASONRY FOUNDATION |
| | SIDEWALL. THE PLANS SPECIFY 7/8" THICK STUCCO ON THE |
| | MASONRY WALLS. THE STUCCO WILL BE REQUIRED TO STOP 6" |
| | ABOVE GRADE UNLESS IT IS LESS THAN 5/8 INCH THICK. |
| | |
| | 7) R314.3 SMOKE ALARMS SHALL BE INSTALLED IN THE |
| | FOLLOWING LOCATIONS: |
| | 1. IN EACH SLEEPING ROOM. |
| | 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| | VICINITY OF THE BEDROOMS. |
| | 3. ON EACH ADDITIONAL STORY OF THE DWELLING, INCLUDING |
| | BASEMENTS AND HABITABLE ATTICS BUT NOT INCLUDING CRAWL |
| | SPACES AND UNINHABITABLE ATTICS. IN DWELLINGS OR |
| | DWELLING UNITS WITH SPLIT LEVELS AND WITHOUT AN |
| | INTERVENING DOOR BETWEEN THE ADJACENT LEVELS, A SMOKE |
| | ALARM INSTALLED ON THE UPPER LEVEL SHALL SUFFICE FOR |
| | THE ADJACENT LOWER LEVEL PROVIDED THAT THE LOWER LEVEL |
| | IS LESS THAN ONE FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | 8) FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN |
| | 10 FEET OF EACH SLEEPING ROOM. |
| | |
| | 9) R302.6 DWELLING/GARAGE FIRE SEPARATION. THE GARAGE |
| | SHALL BE SEPARATED FROM ALL HABITABLE ROOMS ABOVE THE |
| | GARAGE BY NOT LESS THAN 5/8-INCH TYPE X GYPSUM BOARD OR |
| | EQUIVALENT. |
| | |
| | |