2015-12-22 13:33:011- FLAT ROOF LIQUID ROOFING NOA 13-0204.17 SUBMITTED:
 A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF 2010 FBC.
 NOTE: THREE ASSEMBLIES WITH DESIGN PRESSURES OF -60PSF
 WERE UNDERLINED ON NOA SUBMITTED. THESE THREE
 ASSEMBLIES ARE FOR INSULATED ROOF SYSTEMS. PLANS DON'T
 SPECIFY INSULATED ROOF SYSTEMS. CLARIFY/REVISE AS
 REQUIRED TO MATCH.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES OF SEC. R301.
 NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION
 #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW ENHANCED
 FASTENING. SEE GENERAL LIMITATION #9 ON-LAST PAGE OF
 NOA SUBMITTED.
  