| 2015-12-22 13:33:01 | 1- FLAT ROOF LIQUID ROOFING NOA 13-0204.17 SUBMITTED: | | | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301 OF 2010 FBC. | | | NOTE: THREE ASSEMBLIES WITH DESIGN PRESSURES OF -60PSF | | | WERE UNDERLINED ON NOA SUBMITTED. THESE THREE | | | ASSEMBLIES ARE FOR INSULATED ROOF SYSTEMS. PLANS DON'T | | | SPECIFY INSULATED ROOF SYSTEMS. CLARIFY/REVISE AS | | | REQUIRED TO MATCH. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN | | | PRESSURES OF SEC. R301. | | | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION | | | #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW ENHANCED | | | FASTENING. SEE GENERAL LIMITATION #9 ON-LAST PAGE OF | | | NOA SUBMITTED. | | | |
|