| 2015-12-21 18:26:56 | RESIDENTIAL (R3) ADDITION/ALTERATION, THIRD BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- FLAT ROOF LIQUID ROOFING NOA 13-0204.17 SUBMITTED: |
| | A) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301 OF 2010 FBC. |
| | NOTE: THREE ASSEMBLIES WITH DESIGN PRESSURES OF -60PSF |
| | WERE UNDERLINED ON NOA SUBMITTED. THESE THREE |
| | ASSEMBLIES ARE FOR INSULATED ROOF SYSTEMS. PLANS DON'T |
| | SPECIFY INSULATED ROOF SYSTEMS. CLARIFY/REVISE AS |
| | REQUIRED TO MATCH. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES OF SEC. R301. |
| | NOTE: ASSEMBLIES THAT ARE LIMITED BY GENERAL LIMITATION |
| | #9 CAN NOT BE USED BECAUSE THEY DON'T ALLOW ENHANCED |
| | FASTENING. SEE GENERAL LIMITATION #9 ON-LAST PAGE OF |
| | NOA SUBMITTED. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED: |
| | A) REVISE FORM 402-2010. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION.: |
| | (1)ANSWERS FOR ITEMS #6(A) IS INCORRECT. SEE GENERAL |
| | INSTRUCTION NOTE #2 ON FIRST PAGE OF FORM. |
| | |
| | (2) NEED TO ANSWER ITEM #6(B). SEE GENERAL INSTRUCTION |
| | NOTE #2 ON FIRST PAGE OF FORM. |
| | |
| | (3) ITEM # 8(A). THERE IS NOT R-VALUE REQUIREMENT FOR |
| | FOR SLAB ON GRADE. ON THE OTHER HAND, ANY R-VALUE IS |
| | FOR THE INSULATION MATERIAL ONLY. SEE NOTE #3 ON SECOND |
| | PAGE OF FORM SUBMITTED. |
| | |
| | (4) ITEM #9 IS INCORRECT. INSULATION ON CONCRETE BLOCK |
| | WALL NEED TO COMPLY WITH NOTE #3 ON SECOND PAGE OF FORM |
| | SUBMITTED. |
| | NOTE: NEED TO COMPLY WITH THE R-VALUE FOR THE INTERIOR |
| | AND EXTERIOR OF THE WALL. |
| | |
| | (5) ITEM #14. A/C EQUIPMENT IS NOT ALLOWED TO BE |
| | OVERSIZED. SEC. 403.6.1.1 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 3- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR WINDOWS |
| | U-FACTOR AND SHGC FACTOR SHOWN ON THE ENERGY |
| | CALCULATIONS. SEC. 103.2.2 AND SEC. 303.1.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | NOTE: THE ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES |
| | THE PLAN REVIEW FEE IF THE ENERGY CALCULATIONS ARE |
| | DENIED FOR A FOURTH TIME. SEE F.S. 553.80(2)(B) |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | |