2015-09-18 18:51:591- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON
 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW
 SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL
 WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 *** RESPONSE:
 PROVIDE COMPLETE INFORMATION. ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE FL6623-R2 WAS SUBMITTED. AND, NEED
 TO IDENTIFY THE SELECTED ASSEMBLY.
 NOTE: ROOF LIQUID APPLIED ROOF SYSTEM FL6623-R2
 SUBMITTED SHOW ONLY ONE PRODUCT FOR WOOD DECKS. IT'S
 NOA 08-1112.14. THIS NOA EXPIRED ON 01/01/14. THEREFORE
 CAN'T NOT BE USED. NEED TO PROVIDE ANOTHER ROOF PRODUCT
 APPROVAL. KEEP IN MIND THAT IF SELECTED FLAT ROOF
 ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY
 R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL
 BE REQUIRED. ALSO, REVISE DRAWINGS ACCORDING TO FLAT
 ROOF PRODUCT APPROVAL SELECTED.
  