| Plan Review Notes For Permit 14120697 |
| Permit Number |
14120697 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-09-18 18:51:59 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON | | | 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW | | | SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL | | | WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL. | | | | | | *** RESPONSE: | | | PROVIDE COMPLETE INFORMATION. ONLY THE FLORIDA PRODUCT | | | APPROVAL COVER PAGE FL6623-R2 WAS SUBMITTED. AND, NEED | | | TO IDENTIFY THE SELECTED ASSEMBLY. | | | NOTE: ROOF LIQUID APPLIED ROOF SYSTEM FL6623-R2 | | | SUBMITTED SHOW ONLY ONE PRODUCT FOR WOOD DECKS. IT'S | | | NOA 08-1112.14. THIS NOA EXPIRED ON 01/01/14. THEREFORE | | | CAN'T NOT BE USED. NEED TO PROVIDE ANOTHER ROOF PRODUCT | | | APPROVAL. KEEP IN MIND THAT IF SELECTED FLAT ROOF | | | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY | | | R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL | | | BE REQUIRED. ALSO, REVISE DRAWINGS ACCORDING TO FLAT | | | ROOF PRODUCT APPROVAL SELECTED. | | | |
|