| Date |
Text |
| 2015-09-17 16:15:30 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1-BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) TO |
| | VERIFY IF IMPACT FEES ARE ASSESSED. BRING BACK COUNTY |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| | UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2-PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAILS. |
| | NOTE: BUCK SIZE NEEDS TO PROVIDE FULL SUPPORT TO THE |
| | DOOR/WINDOW FRAME. SEE SEC. R612.10.2.1 OF 2010 |
| | FBC-RESIDENTIAL. |
| | ***RESPONSE: |
| | A) DETAIL 4/A-5 DOESN'T SPECIFY WINDOW BUCK SIZE. NOTE: |
| | "BUCKS SHALL EXTEND BEYOND THE INTERIOR FACE OF THE |
| | WINDOW OR DOOR FRAME SUCH THAT FULL SUPPORT OF THE |
| | FRAME IS PROVIDED". SEE SEC. R612.10.2.1 OF 2010 |
| | FBC-RESIDENTIAL AND PRODUCT APPROVALS SUBMITTED. REVISE |
| | DETAIL AS REQUIRED. |
| | B) SIZE OF DOOR BUCK SPECIFIED ON DETAIL 5/A-5 DOESN'T |
| | PROVIDE DOOR FRAME FULL SUPPORT. NOTE: "BUCKS SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME SUCH THAT FULL SUPPORT OF THE FRAME IS PROVIDED". |
| | SEE SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL AND |
| | PRODUCT APPROVALS SUBMITTED. REVISE DETAIL AS REQUIRED. |
| | AND CLARIFY WHAT'S "2"X4" DOOR METAL BUCK"?. SEE DOOR |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) NEW WINDOWS THAT MEET THE DESIGN PRESSURES |
| | CALCULATED BY THE ENGINEER ON SHEET A-3.. |
| | ***RESPONSE: |
| | (1) FLORIDA PRODUCT APPROVAL FL5455-R6 SUBMITTED SAYS |
| | "PENDING FBC APPROVAL". NEED APPROVED PRODUCT APPROVAL. |
| | |
| | (2) PROVIDE COMPLETE REPORT ONLY SHEETS 1 OF 6 AND 2 OF |
| | 6 WERE SUBMITTED. NEED COMPLETE DRAWINGS. |
| | |
| | B) NEW DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED |
| | BY THE ENGINEER ON SHEET A-3. |
| | *** RESPONSE: |
| | PROVIDE COMPLETE DOOR DRAWINGS. ONLY SHEET 1 OF 7 WAS |
| | SUBMITTED. AND MARK TYPE OF JAMB TO BE USED: WOOD OR |
| | PVC?. |
| | |
| | C) NEW ROOF SYSTEM. NOTE: SHINGLES ARE NOT ALLOWED ON |
| | 1/4 PER 12 PITCH. PROVIDE PRODUCT APPROVAL FOR LOW |
| | SLOPE ROOF. CLEARLY IDENTIFY ON THE PRODUCT APPROVAL |
| | WHICH APPROVED ASSEMBLY IS GOING TO BE USED. AND |
| | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF |
| | SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| | REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| | *** RESPONSE: |
| | PROVIDE COMPLETE INFORMATION. ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE FL6623-R2 WAS SUBMITTED. AND, NEED |
| | TO IDENTIFY THE SELECTED ASSEMBLY. |
| | NOTE: ROOF LIQUID APPLIED ROOF SYSTEM FL6623-R2 |
| | SUBMITTED SHOW ONLY ONE PRODUCT FOR WOOD DECKS. IT'S |
| | NOA 08-1112.14. THIS NOA EXPIRED ON 01/01/14. THEREFORE |
| | CAN'T NOT BE USED. NEED TO PROVIDE ANOTHER ROOF PRODUCT |
| | APPROVAL. KEEP IN MIND THAT IF SELECTED FLAT ROOF |
| | ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES REQUIRED BY |
| | R301, THEN SIGNED AND SEALED RAS 117 CALCULATIONS WILL |
| | BE REQUIRED. ALSO< REVISE DRAWINGS ACCORDING TO FLAT |
| | ROOF PRODUCT APPROVAL SELECTED. |
| | |
| | D) VENTED ALUMINUM SOFFIT NOA 13-0402.02. PROVIDE |
| | COMPLETE NOA. ONLY THE COVER PAGE AND PAGE 2 OF 3 WAS |
| | SUBMITTED. |
| | |
| | 4- ENGINEER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: |
| | A) OWNER/AGENT TO CERTIFY/DATE AT THE BOTTOM OF FORM |
| | SUBMITTED. |
| | |
| | B) REVISE FORM 402-2010. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION.: |
| | (1)ITEM #1 IS INCORRECT. ARE THE CALCULATIONS FOR |
| | ENTIRE HOUSE OR FOR JUST THE ENCLOSED ADDITION. |
| | |
| | (2)ANSWERS FOR ITEMS #6(A), #6(B) AND #10(A) ARE |
| | INCORRECT. SEE GENERAL INSTRUCTION NOTE #2 ON FIRST |
| | PAGE OF FORM. |
| | |
| | (3) REVISE ITEM #10. SEE GENERAL INSTRUCTION NOTE #2 ON |
| | FIRST PAGE OF FORM. |
| | |
| | (4) COMPLETE ITEM #12. PROVIDE EQUIPMENT SIZING |
| | CALCULATIONS AS REQUIRED BY SEC. 401.2 AND SEC. |
| | 403.6.1.1 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 6-PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW GETTING THE R- 9.06 VALUE ON THE FLOOR AS SPECIFIED |
| | ON THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | NOTE: ONLY THE R VALUE OF THE INSULATION NEEDS TO BE |
| | CONSIDERED. SEE NOTE#3 ON SECOND PAGE OF ENERGY |
| | CALCULATIONS SUBMITTED. |
| | |
| | 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING |
| | HOW GETTING THE R-10.06 ON MASONRY WALLS AS SPECIFIED |
| | ON THE ENERGY CALCULATIONS SUBMITTED. SEC. 103.2.2 OF |
| | 2010 FBC-ENERGY CONSERVATION. |
| | NOTE: ONLY THE R VALUE OF THE INSULATION NEEDS TO BE |
| | CONSIDERED. SEE NOTE#3 ON SECOND PAGE OF ENERGY |
| | CALCULATIONS SUBMITTED. |
| | |
| | 8- PROVIDE MANUFACTURER'S SPECIFICATIONS FOR WINDOWS |
| | U-FACTOR AND SHGC FACTOR SHOWN ON THE ENERGY |
| | CALCULATIONS. SEC. 103.2.2 AND SEC. 303.1.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER CLEARLY ADDRESSING |
| | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| | |