| Plan Review Notes For Permit 14120697 |
| Permit Number |
14120697 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-02-19 11:39:48 | | | | 14120697 | | | 828 HILLCREST BLVD | | | SF ADDITION | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL RISER PLAN WHICH SHOWS THE MAIN | | | DISCONNECT, PANEL BOARDS, METERS AND FEEDERS. INDICATE | | | ON THE PLAN WHERE THE PANELS ARE LOCATED AND WHERE THE | | | MAIN DISCONNECTS ARE LOCATED. INCLUDE A PANEL SCHEDULE | | | FOR EACH PANEL. SHOW THE SERVICE GROUNDING. NEC 110.2, | | | 110.26, 215.5 | | | | | | A MAIN ELECTRICAL DISCONNECT IS REQUIRED AT THE POINT | | | OF SERVICE. NEC 230.70 | | | | | | PROVIDE A DETAIL FOR THE OVERHEAD SERVICE DROP WHICH | | | PROVIDES 8 FEET OF CLEARANCE AND SHOWS HOW THE MAST | | | WILL BE SUPPORTED. NEC 230.22, 230.28 | | | | | | INDICATE THE SIZE OF THE BRANCH CIRCUIT TO THE AIR | | | CONDITIONING. SHOW THE MAIN DISCONNECT FOR THE AC | | | EQUIPMENT. NEC | | | | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | | | | GFCI PROTECTED RECEPTACLES ARE REQUIRED IN THE SHED. | | | NEC 210.8, 210.52 | | | | | | ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW | | | GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12 | | | | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | | | | |
|