Plan Review Notes
Plan Review Notes For Permit 14120697
Permit Number 14120697
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-19 11:39:48 
 14120697
 828 HILLCREST BLVD
 SF ADDITION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL RISER PLAN WHICH SHOWS THE MAIN
 DISCONNECT, PANEL BOARDS, METERS AND FEEDERS. INDICATE
 ON THE PLAN WHERE THE PANELS ARE LOCATED AND WHERE THE
 MAIN DISCONNECTS ARE LOCATED. INCLUDE A PANEL SCHEDULE
 FOR EACH PANEL. SHOW THE SERVICE GROUNDING. NEC 110.2,
 110.26, 215.5
  
 A MAIN ELECTRICAL DISCONNECT IS REQUIRED AT THE POINT
 OF SERVICE. NEC 230.70
  
 PROVIDE A DETAIL FOR THE OVERHEAD SERVICE DROP WHICH
 PROVIDES 8 FEET OF CLEARANCE AND SHOWS HOW THE MAST
 WILL BE SUPPORTED. NEC 230.22, 230.28
  
 INDICATE THE SIZE OF THE BRANCH CIRCUIT TO THE AIR
 CONDITIONING. SHOW THE MAIN DISCONNECT FOR THE AC
 EQUIPMENT. NEC
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED IN THE SHED.
 NEC 210.8, 210.52
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL NEW
 GENERAL PURPOSE OUTLETS INCLUDING LIGHTING. NEC 210.12
  
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  