| 2015-03-11 10:15:31 | 3/11/2015 |
| | PROJECT: DUNBAR BLDG 3 CLUBHOUSE |
| | PERMIT#: 14120688 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | SHEET E3.1 |
| | 1) REVISE THE FEEDER SCHEDULE KEY NOTES. THE 11/4" |
| | CONDUIT INDICATED IN KEY NOTES 2 AND 3 IS NOT ADAQUATE |
| | TO SUPPORT THE 4, 4/0 CONDUCTORS. NEC ANNEX C |
| | 2) PROVIDE A FAULT CURRENT STUDY TO DETERMINE THE |
| | VAULUE OF THE FAULT CURRENT AVAILABLE AT THE EQUIPMENT. |
| | I DENTIFY THE FAULT CURRENT RATING OF THE EQUIPMENT |
| | PROPOSED TO VERIFY IF WILL BE EQUIPPED WITH A 3) FAULT |
| | CURRENT RATING THAT IS SUFFICIENT AT NOMINAL CIRCUIT |
| | VOLTAGE FOR THE CURRENT THAT MUST BE INTERRUPTED. NEC |
| | 110.9 |
| | 4) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | 5) VERIFY SUFFICIENT ACCESS AND WORKING SPACE IS |
| | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT |
| | TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF |
| | SUCH EQUIPMENT. NEC110.26 |
| | 6) REVISE SIZE OF GROUNDING ELECTRODE CONDUCTOR FOR |
| | CONSISTANCY. THE RISER DIAGRAM INDICATES A #3 GEC BUT |
| | THE GROUNDING DETAIL AND NOTES ON SHEET E5.1 INDICATE |
| | THE USE OF A #3/0 CU GEC. FBC107 |
| | |
| | SHEET E4.1 |
| | ADD NOTE 4 TO CIRCUIT #31 FOR EXTERIOR LIGHTING |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, WIND LOAD |
| | ENGINEERING ARE REQUIRED FOR SITE LIGHTING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |