Plan Review Notes
Plan Review Notes For Permit 14120688
Permit Number 14120688
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-03 08:29:461) SHT.A-1.04 REFERS TO THE USE OF MOISTURE RESISTANT
 GYPSUM BOARD IN WET AREAS. PLEASE REFER TO FBC SEC.
 2509.3 FOR LIMITATIONS.
 2) SHT.A-5.00 - THE TOILET PAPER DISPENSER SHALL BE
 LOCATED A MIN. OF 7 INCHES AND A MAX. OF 9 INCHES FROM
 THE FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER PER THE FL. ACCESSIBILITY
 CODE SEC. 604.7.
 3) SHT.A-5.00 - GRAB BARS SHALL BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM THE FINISH FLOOR NOT TO
 THE CENTERLINE AS SHOWN. 2010 FAC SEC.609.4.
 4) SHT. A-5.00 - THERE ARE REFERENCES TO CODE SECTIONS
 AND FIGURE NUMBERS OF CHAPTER 11 OF THE 2010 FAC. THESE
 CODE SECTIONS OR FIGURE NUMBERS DO NOT EXIIST IN THE
 2010 FBC. PLEASE REVISE TO REFLECT THE CORRECT CODE
 SECTIONS AND FIGURE NUMBERS. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 5) SHT.A-5.01 - BATH PLAN A - THE PLAN VIEW SHOWS THE
 MEASUREMENT TO THE CENTERLINE OF THE WATER CLOSET AS 18
 INCHES MINIMUM. THE DISTANCE SHALL BE 16-18 INCHES FROM
 THE SIDE WALL PER THE 2010 FBC SEC.604.2.
 6) SHT.A-5.01 - BATH PLANS A,B & C - ELEVATIONS A & B
 SEEM TO BE IN CONFLICT REGARDING THE HEIGHT OF THE
 WATER CLOSET SEAT ABOVE THE FINISH FLOOR. ELEVATION A
 SHOWS THE HEIGHT MEASURED TO THE TOP OF THE SEAT WHICH
 IS CORRECT BUT ELEVATION B APPEARS TO HAVE THE
 MEASUREMENT TO THE TOP OF THE TOILET BOWL. COMPLY WITH
 THE 2010 FAC SEC.604.4.
 7) SHT. A-5.01 - THE GRAB BARS IN THE ELEVATION DETAILS
 SHALL BE MEASURED FROM THE FINISH FLOOR TO THE TOP OF
 THE GRIPPING SURFACE PER SEC. 609.4 OF THE 2010 FAC.
 8) SHT.A-5.01 - THE ACCESSORY SCHEDULE LISTS AN ADA
 SHOWERHEAD BUT THE LOCATION IS NOT SHOWN ON THE PLAN.
 CLARIFY.
 9) SHOW THE LOCATION OF THE SHOWER CONTROLS IN BATH
 PLAN. COMPLY WITH 2010 FAC SEC.608.5.2 & 608.6.
 10) SHT. P-1.1 - SHOWS A BACKWATER VALVE ON THE
 SANITARY LINE. BACKWATER VALVES SHALL ONLY BE INSTALLED
 WHEN THE FLOOD LEVEL RIM OF PLUMBING FIXTURES ARE BELOW
 THE ELEVATION OF THE MANHOLE COVER OF THE NEXT
 UPSTREAMMANHOLE IN THE PUBLIC SEWER PER FPC SEC. 715.1.
 REMOVE THE BACKWATER VALVE.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR