2015-02-06 15:39:27820 GRANT STREET - CLUBHOUSE
 PERMIT #14120688
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 GENERAL: STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A-0.01: THE TURNING RADIUS APPEARS TO BE TOO
 SMALL TO ACCOMODATE A 47'-0" LONG LADDER TRUCK FOR THE
 PARKING LOT ACCESS ROAD DIRECTLY SOUTH OF THE CLUBHOUSE
 (NOT THE DROP-OFF AREA).
  
 SHEET A-0.04: ANOTHER EXIT SIGN IS NEEDED OUTSIDE THE
 LOUNGE, OTHERWISE THE COMMON PATH OF TRAVEL EXCEEDS 20
 FOR AN AREA SERVING MORE THAN 50 PERSONS. PANIC
 HARDWARE WILL BE NEEDED ON THE LOUNGE DOOR.
  
 SHEET A-0.04: INDICATE THE LOCATION/TRAVEL TO THE
 PUBLIC WAY FOR THE NORTH EXIT.
  
 SHEET A-0.04: UTILITY (LAUNDRY) ROOMS SHALL BE PROVIDED
 WITH A 1-HOUR FIRE SEPARATION AND AUTOMATIC SPRINKLER
 PROTECTION PER SECTION 12.3.2.1.2(2)(A) OF NFPA 101.
  
 SHEET A-1.01: PROVIDE A PROPOSED FURNITURE LAYOUT TO
 SUPPORT THE USE OF THE 15 SQ.FT. PER PERSON OCCUPANT
 LOAD FACTOR.
  
 SHEET A-6.01: FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD OF 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA
 BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON
 DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR
 LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE
 PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE
 MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED
 DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN
 STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING
 IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN
 HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN "OPEN/LOCKED"
 INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR).
 A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE
 SUBSTITUTED FOR A KEYED LOCK.
  
 SHEET E-1.1: COULD NOT LOCATE ANY EXIT SIGNS OR
 EMERGENCY LIGHTS.
  
 SHEET FA0.1: FIRE ALARM SYSTEM SHALL BE FULLY
 ADDRESSABLE. A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 SHEET FA1.1: INSUFFICIENT NOTIFICATION APPLIANCES
 PROVIDED. ADDITIONALLY, PROVIDE AN EXTERIOR
 NOTIFICATION DEVICE TO ALERT EMERGENCY RESPONDERS
 PROMPTLY.
  