| 2015-02-06 15:39:27 | 820 GRANT STREET - CLUBHOUSE |
| | PERMIT #14120688 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | |
| | GENERAL: STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| | FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| | 69A-60.0081. |
| | |
| | GENERAL: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED |
| | SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED |
| | IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE |
| | ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | SHEET A-0.01: THE TURNING RADIUS APPEARS TO BE TOO |
| | SMALL TO ACCOMODATE A 47'-0" LONG LADDER TRUCK FOR THE |
| | PARKING LOT ACCESS ROAD DIRECTLY SOUTH OF THE CLUBHOUSE |
| | (NOT THE DROP-OFF AREA). |
| | |
| | SHEET A-0.04: ANOTHER EXIT SIGN IS NEEDED OUTSIDE THE |
| | LOUNGE, OTHERWISE THE COMMON PATH OF TRAVEL EXCEEDS 20 |
| | FOR AN AREA SERVING MORE THAN 50 PERSONS. PANIC |
| | HARDWARE WILL BE NEEDED ON THE LOUNGE DOOR. |
| | |
| | SHEET A-0.04: INDICATE THE LOCATION/TRAVEL TO THE |
| | PUBLIC WAY FOR THE NORTH EXIT. |
| | |
| | SHEET A-0.04: UTILITY (LAUNDRY) ROOMS SHALL BE PROVIDED |
| | WITH A 1-HOUR FIRE SEPARATION AND AUTOMATIC SPRINKLER |
| | PROTECTION PER SECTION 12.3.2.1.2(2)(A) OF NFPA 101. |
| | |
| | SHEET A-1.01: PROVIDE A PROPOSED FURNITURE LAYOUT TO |
| | SUPPORT THE USE OF THE 15 SQ.FT. PER PERSON OCCUPANT |
| | LOAD FACTOR. |
| | |
| | SHEET A-6.01: FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT |
| | LOAD OF 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA |
| | BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON |
| | DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE |
| | MAIN ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED |
| | DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN |
| | STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING |
| | IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| | HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN "OPEN/LOCKED" |
| | INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 OR SIMILAR). |
| | A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| | SUBSTITUTED FOR A KEYED LOCK. |
| | |
| | SHEET E-1.1: COULD NOT LOCATE ANY EXIT SIGNS OR |
| | EMERGENCY LIGHTS. |
| | |
| | SHEET FA0.1: FIRE ALARM SYSTEM SHALL BE FULLY |
| | ADDRESSABLE. A CERTIFICATE OF COMPLETION AND A THIRD |
| | PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| | SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| | INSPECTION. |
| | |
| | SHEET FA1.1: INSUFFICIENT NOTIFICATION APPLIANCES |
| | PROVIDED. ADDITIONALLY, PROVIDE AN EXTERIOR |
| | NOTIFICATION DEVICE TO ALERT EMERGENCY RESPONDERS |
| | PROMPTLY. |
| | |