2015-01-26 16:56:391/26/2015
 PROJECT: DUBAR SENIOR COMPLEX CLUBHOUSE
 PERMIT#: 14120688
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E1.1
 A.) PROVISIONS SHALL BE MADE TO PROVIDE EMERGENCY
 ILLUMINATION AND EXIT LIGHTING FOR SAFE MEANS OF EGRESS
 TO A PUBLIC RIGHT OF WAY. NFPA 101, 7.10.1.5.1, NEC
 700.16, NEC 700.12
 B.) CHANGE THE MOTION SENSOR SWITCH IN THE ELECTRICAL
 ROOM TO A STANDARD TOGGLE SWITCH. FBC ENERGY 505.2.2
 EX(4) SPACES WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER
 OCCUPANT SAFETY OR SECURITY.
 C.) IDENTIFY THE OUTLET FOR THE DRINKING FOUNTAIN AS
 GFCI PROTECTED. ELECTRIC DRINKING FOUNTAINS SHALL BE
 PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER
 PROTECTION. NEC 422.52
 D.) PROVISIONS SHALL BE MADE FOR THE REQUIRED WORKING
 CLEARANCE, DISCONNECTING MEANS AND ACCESS TO ELECTRICAL
 EQUIPMENT FOR THE A/C AHU IN THE ATTIC SPACE. SEE NEC
 110.33(B), NEC 440.11, FBC-M 306.3.2
 E.) PROVIDE A SWITCHED LIGHT AT THE ATTIC ACCESS FOR
 ILLUMINATION AT ELECTRICAL EQUIPMENT. SEE NEC 210.70(3)
  
 2) SHEET E3.1
 THE PROPOSED ELECTRICAL RISER DIAGRAM MAKES REFFRENCE
 TO A GROUNDING ELECTRODE DETAIL ON SHEET E8.3 HOWEVER
 THERE IS NO SHEET E8.3 IN THIS SUBMITTAL PACKAGE.
 PLEASE CLARIFY. WPB AMENDMENTS TO FBC 107.2
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  