| | PROJECT: DUBAR SENIOR COMPLEX CLUBHOUSE |
| | PERMIT#: 14120688 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET E1.1 |
| | A.) PROVISIONS SHALL BE MADE TO PROVIDE EMERGENCY |
| | ILLUMINATION AND EXIT LIGHTING FOR SAFE MEANS OF EGRESS |
| | TO A PUBLIC RIGHT OF WAY. NFPA 101, 7.10.1.5.1, NEC |
| | 700.16, NEC 700.12 |
| | B.) CHANGE THE MOTION SENSOR SWITCH IN THE ELECTRICAL |
| | ROOM TO A STANDARD TOGGLE SWITCH. FBC ENERGY 505.2.2 |
| | EX(4) SPACES WHERE AN AUTOMATIC SHUTOFF WOULD ENDANGER |
| | OCCUPANT SAFETY OR SECURITY. |
| | C.) IDENTIFY THE OUTLET FOR THE DRINKING FOUNTAIN AS |
| | GFCI PROTECTED. ELECTRIC DRINKING FOUNTAINS SHALL BE |
| | PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER |
| | PROTECTION. NEC 422.52 |
| | D.) PROVISIONS SHALL BE MADE FOR THE REQUIRED WORKING |
| | CLEARANCE, DISCONNECTING MEANS AND ACCESS TO ELECTRICAL |
| | EQUIPMENT FOR THE A/C AHU IN THE ATTIC SPACE. SEE NEC |
| | 110.33(B), NEC 440.11, FBC-M 306.3.2 |
| | E.) PROVIDE A SWITCHED LIGHT AT THE ATTIC ACCESS FOR |
| | ILLUMINATION AT ELECTRICAL EQUIPMENT. SEE NEC 210.70(3) |
| | |
| | 2) SHEET E3.1 |
| | THE PROPOSED ELECTRICAL RISER DIAGRAM MAKES REFFRENCE |
| | TO A GROUNDING ELECTRODE DETAIL ON SHEET E8.3 HOWEVER |
| | THERE IS NO SHEET E8.3 IN THIS SUBMITTAL PACKAGE. |
| | PLEASE CLARIFY. WPB AMENDMENTS TO FBC 107.2 |
| | |
| | 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD |
| | EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |